Code
Text mes-
sage

Cause

Rectification

M

505

No echo avai-
lable

l Level echo can no longer

be detected

l Clean the antenna
l Use a more suitable an-

tenna/sensor

l Remove possible false

echoes

l Optimize sensor position

and orientation

9

.4 Remove interferences

The first measures are:

l

Evaluation of fault messages via the indicating and adjustment
module

l

Checking the 4 … 20 mA signal

l

Treatment of measurement errors

Further comprehensive diagnosis possibilities are offered by a PC with
the software PACTware and suitable DTM.

In many case, the failure reasons can thus be determined and faults
rectified.

Connect a handmultimeter in the suitable measuring range according
to the wiring plan. The following table describes possible errors in the
current signal and helps to remove them:

Error

Cause

Rectification

4 … 20 mA signal
not stable

l Level fluctua-

tions

l Set damping according to the in-

strument via the indicating and
adjustment module or PACTware/
DTM

4 … 20 mA signal
missing

l Electrical con-

nection faulty

l Check connection according to

chapter "Connection steps" and if
necessary, correct according to
chapter "Wiring plan".

l Voltage supply

missing

l Check cables for breaks; repair if

necessary

l Operating vol-

tage too low or
load resis-
tance too high

l Check, adapt if necessary

Current signal
greater than 22 mA
or less than
3.6 mA

l Electronics

module in the
sensor defecti-
ve

l Exchange the instrument or send it

in for repair

Procedure for fault rec-
tification

Check the 4 … 20 mA
signal

VEGAPULS

62 • 4 … 20 mA/HART - two-wire, approval according to LPR radio standard

59