VEGA VEGAPULS 62 (≥ 2.0.0 - ≥ 4.0.0) 4 … 20 mA_HART - two-wire, approval according to LPR radio standard User Manual
Page 45
1
Select the menu item "Additional settins" with [->] and confirm with
[OK]
. With [->] you have to select the menu item "False signal
suppression" and confirm with [OK].
2
Confirm again with [OK].
3
Confirm again with [OK].
4
Confirm again with [OK] and enter the actual distance from the
sensor to the product surface.
5
All interfering signals in this section are detected by the sensor
and stored after confirming with [OK].
Note:
Check the distance to the product surface, because if an incorrect (too
large) value is entered, the existing level will be saved as false signal.
The filling level would then no longer be detectable in this area.
If a false signal suppression is already created in the sensor, then the
following menu window appears when selecting "False signal
suppression":
The menu item "Delete" is used to completely delete an already
created false signal suppression. This is useful if the saved false signal
suppression no longer matches the metrological conditions in the
vessel.
VEGAPULS
62 • 4 … 20 mA/HART - two-wire, approval according to LPR radio standard
45
6 Set up with the indicating and adjustment module
41718
-EN