2 setup steps – VEGA PLICSRADIO R62 Wireless processing unit User Manual
Page 16
16
6 Setup with the integrated display and adjustment unit
PLICSRADIO C62 • Wireless processing unit for PLICSRADIO T62
32627-EN-130701
– Jump to next higher menu
Note:
Approx. 10 minutes after the last pressing of a key, an automatic reset
to measured value indication is triggered. Any values not confirmed
with [OK] will not be saved.
6.2 Setup steps
The instrument is adapted to the individual application conditions via
parameter adjustment. Configuration of the measurement loops has
priority here. The measurement loop configuration depends on the
use of the emitting units (PLICSRADIO T61 or T62) and the number of
measurements. Unused measurement loops must be deactivated so
that there is no fault pending (see Reset on Measurement Loop).
Instruments with Ethernet interface can be provided with a Host name
suitable for the measurement loop. As an alternative to the addressing
via DHCP, it is also possible to adjust an IP address and subnet mask
suitable for your network. If necessary, the e-mail/Web server can be
also configured with PACTware.
Information:
When using PACTware and the corresponding VEGA DTM, additional
settings can be carried out which are not possible or only partly pos-
sible with the integrated display and adjustment unit. When using an
adjustment software, you either need one of the integrated interfaces
(RS232/Ethernet) or the interface converter VEGACONNECT.
Further instructions for setting up the web server and e-mail functions
are stated in the online help of PACTware or the PLICSRADIO C62
DTMs as well as the supplementary instructions manual "RS232/Eth-
ernet connection".
After being switched on, PLICSRADIO C62 first of all carries out a
short self-check. The following steps are carried out:
•
Internal check of the electronics
•
indication of the instrument type, firmware version as well as the
instrument TAG (instrument name)
•
The output signals jump briefly to the set fault value
Then the current measured values will be displayed and outputted.
As requested, the measured value display shows the individual
measurement loops separately or in a joint overview. The respective
digital display value, the measurement loop name (meas. loop TAG)
and the unit are shown. With the separate presentation, an analogue
bar graph is also displayed and the measured values appear in big-
ger font size. By pushing the [>] key, you move between the different
indicating options.
Note:
Depending on the configuration and use of all measurement loops,
the cycle time for the measured value transmission can take up to five
seconds.
Parameter adjustment
Switch-on phase
Measured value indica-
tion