4 mounting, 1 general instructions, 2 mounting instructions – VEGA PLICSRADIO R62 Wireless processing unit User Manual
Page 12
12
4 Mounting
PLICSRADIO C62 • Wireless processing unit for PLICSRADIO T62
32627-EN-130701
4 Mounting
4.1 General instructions
Each series 600 instrument consists of the actual signal conditioning
instrument as well as a plug-in socket for carrier rail mounting (top-
hat rail 35 x 7.5 according to DIN EN 50022/60715). Because it has
protection class IP 30 or IP 20, the instrument is intended to be used
in switching cabinets.
4.2 Mounting instructions
The plug-in socket is designed for carrier rail mounting. The operat-
ing voltage is connected to terminals 17 and 18. For neighbouring
series 600 instruments it is possible to continue connection L1 and
N directly via the supplied bridges. Max. five instruments can be con-
nected through in this way.
Danger:
Looping through via bridges is only allowed for operating voltage
(sockets L1 and N). The bridges must never be used with single
instruments, at the end of a row of instruments or with other sockets.
If this rule is not heeded, there is a danger of coming into contact with
the operating voltage or causing a short circuit.
All signal conditioning instruments are provided with different gaps
dependent on type and version (mechanical coding).
The plug-in socket is provided with coded pins that can be inserted to
prevent accidental interchanging of the various instrument types.
A o
B o
C o
1 o
2 o
3 o
o
o
o
7 o
8 o
9 o
o
o
12 o
N
L1
VEGA
A o
B o
C o
1 o
2 o
3 o
4 o
5 o
6 o
7 o
8 o
9 o
10 o
11 o
12 o
N
L1
VEGA
1 2
3 4
5 6
7 8
2
2
1
Fig. 4: Plug-in socket PLICSRADIO C62
1 Type coding for PLICSRADIO C62
2 Bridges for looping the operating voltage
Installation possibilities
Mounting
Instrument coding