VEGA VEGABAR 64 Profibus PA User Manual

Page 65

background image

Byte-No.

1

2

3

4

5

6

7

8

9

10

Format

Value

IEEE-754-

Flieskommazahl

PA-OUT

(FB1)

Status

Status

(FB1)

IEEE-754-

Flieskommazahl

Temperature

(FB2)

Status

Status

(FB2)

Fig. 32: Telegram configuration example 2

Example 3 with pressure value and additional cyclical value without temperature value:

l

AI (PA-OUT)

l

Free Place

l

Additional Cyclic Value

Byte-No.

1

2

3

4

5

6

7

8

9

10

Status

Status

Status

Status

(FB1)

IEEE-754-

Floating point value

PA-OUT

(FB1)

IEEE-754-

Floating point value

Additional Cyclic

Value

Format

Value

Fig. 33: Telegram configuration example 3

Data format of the output signal

Byte4

Byte3

Byte2 Byte1 Byte0

Status

Value (IEEE-754)

Fig. 34: Data format of the output signal

The status byte corresponds to profile 3.0 "Profibus PA Profile for Process Control Devices" coded.
The status "Measured value OK" is coded as 80 (hex) (Bit7 = 1, Bit6 … 0 = 0).

The measured value is transferred as a 32 bit floating point number in the IEEE-754 format.

Byte n

Byte n+1

Bit

7

VZ

Exponent

Bit

6
2

Bit

5
2

Bit

4
2

Bit

3
2

Bit

2
2

Bit

1
2

Bit

0
2

Bit

7
2

Bit

6
2

Bit

5
2

Bit

4
2

Bit

3
2

Bit

2
2

Bit

1
2

Bit

0
2

Sign

Bit

Significant

7

6

5

4

3

2

1

0

-1

-2

-3

-4

-5

-6

-7

Byte n+2

Byte n+3

Bit

7
2

Significant

Bit

6
2

Bit

5
2

Bit

4
2

Bit

3
2

Bit

2
2

Bit

1
2

Bit

0
2

Bit

7
2

Bit

6
2

Bit

5
2

Bit

4
2

Bit

3
2

Bit

2
2

Bit

1
2

Bit

0
2

Significant

-9

-10 -11 -12 -13 -14 -15 -16 -17

-18 -19

-20 -21 -22 -23

-8

Value = (-1)

VZ

2

(Exponent - 127)

(1 + Significant)

Fig. 35: Data format of the measured value

VEGABAR

64 • Profibus PA

65

10 Supplement

28252

-

EN