E

041

l

Hardware error, electronics defective

à Exchange instrument or return instrument for repair

?

E

113

l

Communication conflict

à Exchange instrument or return instrument for repair

Depending on the failure reason and measures taken, the steps
described in chapter "Set up" must be carried out again, if necessary.

8.3 Calculation of total deviation (similar to

DIN 16086)

The total deviation F

total

according to DIN 16086 is the sum of basic

accuracy F

perf

and longterm stability F

stab

. F

total

is also called

maximum practical deviation or utility error.

F

total

= F

perf

+ F

stab

F

perf

= √((F

T

)

2

+ (F

Kl

)

2

)

With analogue output, the error of the current output F

a

is also added.

F

perf

= √((F

T

)

2

+ (F

Kl

)

2

+ (F

a

)

2

)

With:

l

F

total

: Total deviation

l

F

perf

: Basic accuracy

l

F

stab

: Long-term drift

l

F

T

: Temperature coefficient (influence of medium or ambient

temperature)

l

F

Kl

: Deviation

l

F

a

: Error current output

Pressure measurement in the pipeline 8 bar (800 KPa)

Product temperature 50 °C, hence within the compensated range

VEGABAR

64 with measuring range 25 bar

Calculation of the set Turn Down: TD = 10 bar/8 bar, TD = 1.25

Basic accuracy digital output signal in percent:
F

perf

= √((F

T

)

2

+ (F

Kl

)

2

)

F

T

= (0.05 % + 0.1 % x TD)

F

Kl

=

0.075 %

F

perf

= √((0.05 % + 0.1 % x 1.25)

2

+ (0.075 %)

2

)

F

perf

=

0.19 %

Reaction after fault rec-
tification

Total deviation

Example

48

VEGABAR

64 • Profibus PA

8 Maintenance and fault rectification