VEGA VEGABAR 64 Profibus PA User Manual

Page 35

background image

Information:
For an adjustment with filling, you simply enter the displayed actual
measured value. If the adjustment ranges are exceeded, the message
"Outside parameter limits" appears. The editing procedure can be
aborted with [ESC] or the displayed limit value can be accepted with
[OK]

.

Proceed as follows:

1

Edit the % value in the menu item "Max. adjustment" with [OK].

Max. adjustment

+100

.0 %

=

+1000

.0 mbar

0000.0 mbar

Information:
The displayed pressure for 100 % corresponds to the nominal
measuring range of the sensor (in the above example 1 bar =
1000 mbar).

2

Set the requested percentage value with [->] and [OK].

3

Edit the requested mbar value with [OK].

4

Set the requested mbar value with [+] and [->].

5

Confirm with [OK] and move to the menu overview with [ESC].

The max. adjustment is finished.

Information:
For an adjustment with filling, you simply enter the displayed actual
measured value. If the adjustment ranges are exceeded, the message
"Outside parameter limits" appears. The editing procedure can be
aborted with [ESC] or the displayed limit value can be accepted with
[OK]

.

Process pressure measurement

Set up VEGABAR 64 in the following sequence:

1

Select application "Process pressure measurement"

2

Select the unit of measurement

3

Carry out position correction

4

Carrying out zero adjustment

5

Carrying out span adjustment

In the menu item "Adjustment unit" you select the physical unit in which
the adjustment should be carried out, e.g. mbar, bar, psi…

The position correction compensates the influence of the mounting
position or static pressure on the measurement. It does not influence
the adjustment values.

Carrying out max. ad-
justment

Parameter ad-
justment "Proc-
ess pressure
measurement"

VEGABAR

64 • Profibus PA

35

6 Set up with the indicating and adjustment module PLICSCOM