VEGA VEGABAR 64 Profibus PA User Manual
Page 64
-
PA-OUT value of the FB1 after scaling
l
Temperature
-
PA-OUT value of the FB2 after scaling
l
Additional Cyclic Value
-
Additional cyclical value (depending on the source)
l
Free Place
-
This module must be used if a value should not be used in the data telegram of the cyclical data
traffic (e.g. replacement of the temperature and Additional Cyclic Value)
Max. three modules can be active. By means of the configuration software of the Profibus master,
you can determine the configuration of the cyclical data telegram with these modules. The procedure
depends on the respective configuration software.
Tip:
The modules are available in two versions:
l
Short for Profibus master supporting only one "Identifier Format"
byte, e.g. Allen Bradley
l
Long for Profibus master only supporting the "Identifier Format"
byte, e.g. Siemens S7-300/400
Examples of telegram configuration
In the following you will see how the modules can be combined and how the appendant data telegram
is structured.
Example 1 (standard setting) with pressure value, temperature value and additional cyclical value:
l
AI (PA-OUT)
l
Temperature
l
Additional Cyclic Value
Byte-No.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
Format
Value
IEEE-754-
Flieskommazahl
PA-OUT
(FB1)
Status
Status
(FB1)
IEEE-754-
Flieskommazahl
Temperature
(FB2)
IEEE-754-
Flieskommazahl
Additional Cyclic
Value
Status
Status
(FB2)
Status
Status
Fig. 31: Telegram configuration example 1
Example 2 with pressure value and temperature value without additional cyclical value:
l
AI (PA-OUT)
l
Temperature
l
Free Place
64
VEGABAR
64 • Profibus PA
10 Supplement
28252
-EN
-081209