VEGAPULS 42, 44 and 45 – 4 … 20 mA
Technical data
Parameter and measuring range
1)
Parameter
distance between product surface and process
fitting (e.g. lower flange side of the sensor)
VEGAPULS 42
- standard
ø 40 mm horn
0 … 10 m
- optional
ø 48 mm horn
0 … 15 m
ø 75, 95 mm horn
0 … 20 m
VEGAPULS 44
- DN 50, ANSI 2“
0 … 15 m
- DN 80, 100, ANSI 3“, 4“, 6“
0 … 20 m
VEGAPULS 45
0 … 4 m
Output signal
Signal output
4 … 20 mA current signal in two-wire or
four-wire technology; the HART
®
signal is
modulated to the 4 … 20 mA signal
Fault signal
current output unchanged, 20.5 mA, 22 mA
(adjustable)
Resistance/Load of the signal cable
- 4 … 20 mA two-wire
non-Ex:
max 975
Ω
Ex d ia:
max. 720
Ω
Ex ia:
max. 670
Ω
- 4 … 20 mA four-wire
500
Ω
Integration time
- analogue 4 … 20 mA
0 … 999 seconds
Two-wire technology 4 … 20 mA:
The analogue 4 … 20 mA output signal (measuring signal) is transmitted together with the
power supply via one two-wire cable.
Four-wire technology 4 … 20 mA:
Separate power supply. The analogue 4 … 20 mA output signal (measuring signal) is
transmitted in a cable separate from power supply.
Measured value display (optional)
Liquid crystal indication
- in the sensor
scalable output of measured values as graph
and number
- in the external indicating instrument
powered by the sensor
scalable output of measured values as graph
and number. The display unit can be mounted
up to 25 m away from the sensor
Adjustment
- PC and adjustment software VEGA Visual Operating
- adjustment module MINICOM
- HART
®
handheld
1)
Min. distance of the antenna to the medium 5 cm (only types 42 and 44)