beautypg.com

6 diagnostics, 1 simulation, 2 error codes – VEGA VEGAPULS 45 4 … 20 mA; HART compact sensor User Manual

Page 52

background image

52

VEGAPULS 42, 44 and 45 – 4 … 20 mA

Diagnostics

6 Diagnostics

6.1 Simulation

To simulate a certain filling level, you can call
up the function “Simulation” in the adjustment
module MINICOM, in the adjustment software
PACT

ware

TM

or in the HART

®

handheld.

You simulate a vessel filling and thereby a
certain sensor current. Please note that con-
nected instruments, such as e.g. a PLC,
react according to their adjustments and will
probably activate alarms or system func-
tions. One hour after the last simulation ad-
justment, the sensor returns automatically to
standard operating mode.

5.2 Error codes

Display

Meaning

Rectifying measure

E013

No valid measured value

Message is displayed during warm-up phase

- Sensor in the warm-up
phase
- Loss of the useful echo

If the message remains, a false echo storage
must be made with the adjustment module
MINICOM in the menu “sensor optimisation” or
better, with the PC and VVO.
If the message still remains, carry out a new
adjustment.

E017

Adjustment span too small

Carry out a readjustment.
Make sure that the difference between
min. and max. adjustment is at least 10 mm.

E036

Sensor software does not

- Sensor must be programmed with new

run

software (service)
- Message appears during a software update.

E040

Hardware failure/Electronics Check all connection cables.
defective

Contact our service department.