VEGAPULS 42, 44 and 45 – 4 … 20 mA

< 135 mm
(250 mm)

3.5 Common installation mistakes

Socket piece too long

If the sensor is mounted in a socket exten-
sion that is too long, strong false echoes are
generated which interfere with the measure-
ment. Make sure that the horn antenna pro-
trudes out of the socket piece.

Flange antenna: Correct and unfavourable socket
length

Flange antenna: Correct and unfavourable socket
length

Unfavour-
able

Correct

Unfavourable

Correct

Reference
plane

75 %

0 %

100 %

Strong product movements

Strong product movements

Strong turbulence in the vessel, e.g. caused
by powerful stirrers or strong chemical reac-
tions, can seriously interfere with the meas-
urement. A surge or bypass tube (see
illustration) of sufficient size always enables
reliable and problem-free measurement even
if strong turbulence occurs in the vessel,
provided there is no product buildup in the
tube.

Mounting and installation

Correct

Incorrect