4

4 ... 20 mA

2

2

2

2

1)

Measuring system with VEGAPULS 56K Ex, 56K Ex 0 with pressure-tight
encapsulated connection compartment on active PLC

• Two-wire technology, supply via the cable from active PLC to Exd connection compartment

for operation in Ex-Zone 1 (VEGAPULS 56K Ex) or Ex-Zone 0 (VEGAPULS 56K Ex 0)

• Output signal 4 … 20 mA (passive).
• Measured value display integrated in the sensor.
• Optional external indicating instrument with analogue and digital display (can be mounted

up to 25 m away from the sensor in Ex area).

• Adjustment with PC, HART

®

handheld or adjustment module MINICOM (can be plugged into

the sensor or into the external indicating instrument VEGADIS 50).

HART

®

handheld

VEGA-
CONNECT 2

Electrical connection

1)

If the resistance of the processing
systems connected to the
4 … 20 mA signal output is less
than 200

Ω, a resistor must be

connected to the connection cable
during adjustment to get a loop
resistance of 250

Ω up to 350 Ω .

The digital adjustment signal would
otherwise be severely damped or
short-circuited due to insufficient
resistance of the connected
processing system. Digital
communication with the PC would
not be ensured.

2)

4 … 20 mA passive means that
the sensor consumes a level-
dependent current of 4 … 20 mA.
The sensor reacts electrically like
a varying resistor (consumer) to
the PLC.

VEGADIS 50 Ex

passive

2)

EEx d ia

Ex area

Non Ex area

PLC

EEx e