Measuring system with VEGAPULS 56K on active PLC
• Two-wire technology, power supply from active PLC.
• Output signal 4 … 20 mA (passive).
• Measured value display integrated in the sensor.
• Optional external indicating instrument (can be mounted up to 25 m away from the sensor in
Ex area).
• Adjustment with PC, HART
®
handheld or the adjustment module MINICOM (can be plugged
into the sensor or into the external indication instrument).
HART
®
handheld
VEGA-
CONNECT 2
Electrical connection
1)
If the resistance of the processing
systems connected to the
4 … 20 mA signal output is less
than 200
Ω, a resistor must be
connected to the connection cable
during adjustment to get a loop
resistance of 250
Ω up to 350 Ω .
The digital adjustment signal would
otherwise be severely damped or
short-circuited due to insufficient
resistance of the connected
processing system. Digital
communication with the PC would
not be ensured.
2)
4 … 20 mA passive means that
the sensor consumes a level-
dependent current of 4 … 20 mA.
The sensor reacts electrically like
a varying resistor (consumer) to
the PLC.
VEGADIS 50
passive
2)
PLC