beautypg.com

VEGA VEGAPULS 56K User Manual

Page 30

background image

30

VEGAPULS 56K

22915-EN-041227

4

-

+

4 ... 20 mA

2

2

2

Measuring system with VEGAPULS 56K Ex, 56K Ex0 via separator (Smart-
Transmitter) on passive PLC

• Two-wire technology (loop powered), intrinsically safe ia supply via the signal cable of the

separator for operation of the sensor in Ex zone 1 (VEGAPULS 56K Ex) or in zone 0
(VEGAPULS 56K Ex0)

• Output signal sensor, 4 … 20 mA passive.
• Output signal separator, 4 … 20 mA active
• Optional external indicating instrument with analogue and digital display (can be mounted

up to 25 m away from the sensor).

• Adjustment with PC, HART

®

handheld or adjustment module MINICOM (can be plugged into

the sensor or into the external indicating instrument VEGADIS 50)

• Max. resistance of the signal cable 15

Ω per wire

Electrical connection

active

1)

VEGA-
CONNECT 2

Separator
(see „3.3 Approvals“)

VEGADIS 50 Ex

PLC

HART

®

handheld

Ex area

Non Ex area

EEx ia

1)

4 … 20 mA active means that the
separator delivers a level-
dependent current of 4 … 20 mA
The separator reacts electrically
to the PLC like a current source.