beautypg.com

VEGA VEGABAR 41 HART User Manual

Page 39

background image

VEGABAR 41 (HART

®

)

39

Diagnostics

Checking pressure compensation

Open the housing of VEGABAR. The meas-
ured value must not change. However, if the
displayed value changes, compensation of
the atmospheric pressure is not ensured,
which will lead to distortion of the measured
value. Check the breather on the VEGABAR
housing.

Checking the electrical components

Voltage

- the terminal voltage on VEGABAR must be

at least 12 V DC

Current

Current value

Condition

3.8 … 20.5 mA

standard range for the output
current

0 mA

signal cable interrupted

< 3.6 mA

sensor electronics or pressure
sensor element defective

22 mA

sensor electronics or pressure
sensor element defective

~

1 2 3

+

+

mA

Voltage

Current

V

External
energy source

Ammeter for local
control

mA