VEGABAR 41 (HART

®

)

37

Setup

Note:

After adjustment of a parameter, push "ENTER“ and then "SEND“.
Confirm the message to switch over to manual operation with "OK“.
Confirm the message to reset to automatic operation also with "OK“.
Only then will the adjustment be stored in the sensor and take effect.

1.2.3.1.1

Generic: SENSOR
Current applied
process value :10.945 mbar

1 Set as 4 mA value
2 Read new value
3 Leave as found

ABORT ENTER

1.2.3.1.2

Generic: SENSOR
Current applied
process value:
85.281 mbar

1 Set as 20 mA value
2 Read new value
3 Leave as found

ABORTENTER

Generic: SENSOR
Choose analog output
level

1 4 mA
2 20 mA
3 Other
4 End

ABORT ENTER

Generic: SENSOR
WARN-Loop should be
removed from
automatic control

ABORT OK

Generic: SENSOR
Ser the:

1 4 mA
2 20 mA
3 Exit

ABORT ENTER

Generic: SENSOR
Apply new 20 ma input

ABORT OK

Generic: SENSOR
Current applied
process value:
85.281 mbar

1 Set as 20 mA value
2 Read new value
3 Leave as found

ABORT ENTER

Generic: SENSOR
Set the :

1 4 mA
2 20 mA
3 Exit

ABORT ENTER

Generic: SENSOR
Apply new 4 ma input

ABORT OK

Generic: SENSOR
Current applied
process value:
10.945mbar

1 Set as 4 mA value
2 Read new value
3 Leave as found

ABORT ENTER

Menu windows are displayed but not
supported by the sensor.
Saving of adjustments carried out here is
therefore not possible.

1.4.3.1.3

1.4.3.1.2

Generic: SENSOR
AO Alrm typ
Lo

EXIT

Low:

In case of failure, current output
goes to 22 mA

High:

In case of failure, current output
goes to < 3.6 mA

1.4.3.2

Generic: SENSOR
HART output

1 Poll addr
2 Num req preams

0

3 Burst mode Off
4 Burst option

HELP SAVE

HOME

1.4.3.1

Generic: SENSOR
Analog output

1 AO1

13.467mA

2 AO Alrm typ Lo
3 Loop test
4 D/A trim
5 Scaled D/A trim

HELP SAVE

HOME

}

Off
On
Not used
Non
Unused
Special

Generic: SENSOR
Fld dev output is
fixed at 4.000 mA

ABORT OK

Sensor signals measured values only on
request
Sensor signals measured values
unrequested

Choice is not supported

1.4.3.2.3

Generic: SENSOR
Burst mode
Off

On
Not used
None
Unknown

ESC ENTER

1.4.3.2.4

Generic: SENSOR
Burst option
*************

PV
% range/current
Process vars/crnt

HELP

ESC ENTER

Leave the Burst-mode in
OFF-position

Choice is not supported

1.2.3.1.1.1

1.2.3.1.2.1

1.4.3.1.3

1.4.3.1.3.1