Hart, Menu schematic, Setup – VEGA VEGABAR 41 HART User Manual
Page 34
34
VEGABAR 41 (HART
®
)
Setup
HART
®
menu schematic
A
Hart Communicator
Self Test
in Progress
Firmware Rev: F2.2
Module Rev: 3.6
01992-96 FRSI
Generic: SENSOR
PV
80.945 mbar
HELP
EXIT
Generic: SENSOR
Device setup
1 Process variables
2 Diag/Service
3 Basic setup
4 Detailed setup
5 Review
SAVE HOME
1
2
3
4
5
1.1
4.1
(5.1)
4.2
(5.2)
Generic: SENSOR
PV URV
100.000 mbar
90.300
mbar
HELP DEL
ESC ENTER
Generic: SENSOR
Process variables
1 Snsr
80.945 mbar
2 AI % rnge
3 AO1 mA
HELP SAVE
HOME
Less important
menu windows
Not required, unimportant
or blocked menu windows
Important and
required
menu windows
B
Switch on:
after approx.
20 s
Set up the sensor in the sequence of the
letters A, B, C and D (adjustment without
medium).
For the adjustment with medium you
setup the sensor in the sequence A1, B1,
C and D.
Generic: SENSOR
Online(Generic)
1 Device setup
2 PV
80.945 mbar
3 PV AO mA
4 PV LRV bar
5 PV URV bar
SAVE
Generic: SENSOR
AO1
16.952 mA
HELP
EXIT
Generic: SENSOR
1 PV
LRV bar
2 PV
URV bar
HELP
HOME
Generic: SENSOR
1 PV LRV bar
2 PV URV bar
HELP
HOME
Generic: SENSOR
1 PV
LRV bar
2 PV
URV bar
HELP SEND
HOME
Generic: SENSOR
– WARNING –
Pressing "OK“ will
change device output.
Put loop in manual.
ABORT OK
continue like under
A figure 4.1(5.1)
Generic: SENSOR
– WARNING –
Return control loop
to automatic control
OK
Generic: SENSOR
1 PV
LRV
bar
2 PV
URV
bar
HELP
HOME
Empty adjustment without
medium
Full adjust-
ment without
medium
Generic: SENSOR
PV LRV
0.000 mbar
10.000
mbar
HELP DEL
ESC
ENTER
continue like under 4