VEGABAR 41 (HART

®

)

23

Setup

Note:

- A modification of zero does not influence

the span, i.e the final value of the measur-
ing range will simply be shifted.

- By pushing the "+“ and "–“ keys, the output

current remains on the last value, after
saving with the "OK“ key, the output current
takes on the adjusted value.

Evaluation

Linearisation curve

Is only displayed, if a linearisation
curve was activated with VVO.

Adjustment of the integration time

An integration time t

i

of 0 s ... 10 s

can be adjusted with the “+” or “-”
key for damping of pressure

shocks. The adjusted value can be saved
with the "OK“ key.

Selection of the indicated unit

The actually measured pressure is
indicated on the DOT-matrix in the
measured value indication. The
appropriate unit can be chosen
with the "+“ or "–“ key and the "OK“
key from a list. When choosing the
unit "Scal.“, the following menu
items are available.

Indication scaling

In operating condition the actual measured
pressure is displayed on the display module:
- as a bar graph with 20 segments
- as a 4-digit digital value.

Bar graph and digital value relate to the ad-
justed measuring range and change in pro-
portion to the current output. Digital values
< –10 % or > 110 % are shown as flashing
figures.

As a result of scaling, the 4 mA or 20 mA
user-specific current output values are sent
to the display module as 4-digit digital val-
ues.

Outputs

Current output/Selection of the character-
istics

The current output provides the actual meas-
ured pressure as an analogue current signal
4 … 20 mA depending on the adjustment.

The characteristics can be also
inverted, i.e. switched to 20 ... 4 mA
with the "+“ or "–“ keys and the
"OK“ key

Fault signal

The fault signal is triggered via the current
output if, during continuous self-monitoring,
failures, damage or interference of the meas-
uring cell or the electronics are detected.

You can choose whether the failure
current should be 22 mA or 3.6 mA
with the "+“ or "–“ keys and the
"OK“ key.

Simulation

You can set with the "+“ or "–“ keys
an individual pressure or %-value to
check the outputs of VEGABAR and
the connected components. The set
value flashes during activated simu-
lation. The simulation can be
stopped with the "OK“ key.

ti

1

s

Lin.-

curve

active

Unit

0.0

mbar

psi
kPa
%
Scal.
mA

Scaling

indica-

tion

100%=

1000

Decimal

point

888.8

0%=

0

Escape

Fault

signal

22mA

3.6mA

Current

output

4-20mA

20-4mA

Simula-

tion

Sim.

xx.x

mbar