7 Diagnostics

7.1 Simulation

To simulate a certain filling, you can call up
the function "Simulation“ on the adjustment
module MINICOM, in the software program
VVO or on the signal conditioning instrument.

You simulate a vessel filling and thereby a
certain sensor current. Please note that con-
nected instruments, such as e.g. a PLC,
react according to their adjustments and will
probably activate alarms or system func-
tions.

Simulation with VVO

If you start the simulation mode with the ad-
justment program VVO on the PC, the simu-
lated level is outputted until you quit the
simulation mode.

Simulation with MINICOM

If you start the simulation mode on the adjust-
ment module MINICOM, the sensor returns to
standard operating mode after one hour.

Diagnostics

7.2 Error codes

Error codes

Corrective measures

E013

No valid measured value

Message is displayed during the warm-up

- Sensor in the warm-up phase

phase

- Loss of the useful echo

If the message remains, a false echo storage
(with the adjustment software on the PC - see
"Echo curve“ under "Sensor optimisation“) must
be carried out together with a modification of
mounting location and orientation to achieve the
lowest possible false echo background.

E017

Adjustment span too small

Carry out a readjustment.
Make sure that the difference between
min. and max. adjustment is at least 10 mm .

E036

Sensor software does not run

Sensor requires a software update (service).

Message appears during a software update.

E040

Hardware failure/Electronics defec-

Check all connection cables.

tive

Transducer defective.
Contact our service department.