2 adjustment with vvo – VEGA VEGASON 51P…53P Profibus PA User Manual
Page 43
VEGASON 51P … 53P
43
6.2 Adjustment with VVO
Before you can adjust the sensors with the
adjustment program VVO (VEGA Visual
Operating), they must be integrated into the
Profibus system. First of all address the
sensors (chapter "5.2 Sensor address“) and
connect them to your PA segment. With the
attached GSD file you integrate the sensors
into your system.
To adjust the VEGA sensors with the adjust-
ment software VVO, the PC or the adjustment
station on which VVO is installed must be
equipped with a Profibus DP interface card
(e.g. of Messrs. Softing). The PC or the ad-
justment station communicates then as Mas-
ter-Class 2 participant on the DP bus with the
VEGA sensors on the PA bus segment.
To connect the PC to the DP bus, a standard
RS 485-DTE interface cable (Data Terminal
equipment) is required. With the cable you
connect the DP interface card to the bus or to
the segment coupler.
PC
BUS
Screen
1
1 Screen
– –
2
2 M24
RxD/TxD-P
3
3 RxD/TxD-P
(40)
– –
4
4 CNTR-P
GND
5
5 GND
(55)
– –
6
6 VP
– –
7
7 P24
RxD/TxD-N
8
8 RxD/TxD-N (41)
– –
9
9 CNTR-P
Profibus-DP
DP bus (in brackets the
interface card
PIN number of the P+F
segment couplers)
Setup
If the computer is connected to the Profibus
DP cable, you can start VVO.
In the following setup and adjustment instruc-
tions you will find information on the following
topics and adjustment items:
•
Configuration
- Configuration info
- Software addressing
- Create new measurement loop
•
Parameter adjustment 1
- Meas. loop data
- Adjustment
- Scaling
•
Sensor optimisation
- Meas. environment/Operating range
- Meas. environment/Meas. conditions
- Meas. environment/Sonic velocity
- Echo curve
- False echo storage
•
Parameter adjustment 2 (optional)
- Linearisation
- Defining the linearisation curve by incre-
mental filling
- Calculating the linearisation curve
- Calculate cylindrical tank
• Display measured value
• Simulation
• Print configuration and adjustments
• Backup
Sensor
Sensor
Sensor
Sensor
VVO
Segment
coupler
Profibus PA
cable
Profibus DP
interface card
(Messrs. Softing)
DP cable