VEGASON 51P … 53P

55

Setup

• Now click in the opening menu window

"

False echo storage“ to

"Learn false ech-

oes“. A small window opens.

• Enter here the verified product distance or

the distance to the vessel bottom and click
to

"Create new“.

You hereby authorise the sensor to mark all
echoes before the product echo as false
echoes. This prevents the sensor from erro-
neously detecting a false echo as level echo.

• Click to

"Show echo curve“.

The false echo marking and the real echo
curve (top) are shown.

• Quit the menu with

"Quit“.

You are again in the menu window "

Sensor

optimisation“. With the menu item "Reset“ you
reset all options out of the menu "

Sensor

optimisation“ to default.

• Quit the menu window "

Sensor optimisa-

tion“ with

"Quit“ and with "Quit“ the menu

window "

Sensor optimisation Sensor

choice“.

You are then in the initial menu window "

In-

strument data parameter adjustment“.