VEGA VEGASON 51P…53P Profibus PA User Manual
Page 48
48
VEGASON 51P … 53P
Setup
• Click to the sensor or the measurement
loop for which you want to carry out the
parameter adjustment.
• Then click to "
OK“, the menu window "In-
strument data parameter adjustment“
opens.
Measurement loop data
• When clicking "
Meas. loop data“, the most
important measurement loop data will be
displayed.
Adjustment
• Click to "
Adjustment“.
• Click in the menu window "
Adjustment“ to
"
Min/Max-Adjustment“.
You can carry out the min./max. adjustment
"with medium“ (adjustment by means of the
real level) or
"without medium“ (without taking
the real level into account, i.e. with empty
vessel).
Generally, you will carry out the adjustment
without medium, so you are completely inde-
pendent of the actual vessel filling during the
adjustment. If you want to carry out the ad-
justment with medium, you have to carry out
the min. adjustment with emptied (also partly
emptied) vessel and the max. adjustment
with filled (also partly filled vessel). It is there-
fore easier and faster to carry out the adjust-
ment without medium.
• Click to "
Quit“ and you are again in the
menu window "
Instrument data parameter
adjustment“.