Technical data

Display of measured value (optional)

Liquid crystal display
- in the sensor

scalable output of measured value as graph and
as numerical value

- external, powered by the sensor

scalable output of measured value as graph and

as numerical value, display can be separated
up to 25 m from the sensor

Accuracy

1)

(typical values under reference conditions, all information relates to the nominal measuring
range)

Characteristics

linear

Deviation in characteristics including

linearity, reproducibility and
hysteresis (determined acc. to the
limit point method)

< 0.1 %

Linearity

better than 0.05 %

Average temperature coefficient of the
zero signal

0.06 %/10 K

Resolution general

max. 1 mm

Resolution of the output signal

0.005 % or 1 mm

Characteristics

1)

(typical values under reference conditions, all information relates to the nominal measuring
range)

Min. span between

full and empty

> 20 mm (recommended > 50 mm)

Ultrasonic frequency (at 20°C)
- VEGASON 51

70 kHz

- VEGASON 52

55 kHz

- VEGASON 53

34 kHz

Meas. intervals

1.0 s

Beam angle (at –3 dB acoustic power)
- VEGASON 51

5.5°

- VEGASON 52

5.5°

- VEGASON 53

Influence of the ambient temperature

negligible, is compensated by a dynamic
temperature detection integrated in the
transducer. The ambient temperature error
without temperature compensation is 0.18 %/K

Influence of the process pressure

negligible within the approved sensor pressures

Adjustment time

2)

> 2 s (depending on the parameter adjustment)

1)

Similar to DIN 16 086, reference conditions according to IEC 770, e.g.
temperature 15°C … 35°C; moisture 45 % … 75 %; pressure 860 mbar … 1060 mbar

3)

The adjustment time (also actuating time, response time or adjustment period) is the time the sensor
requires to output the correct level (with max. 10% deviation) after a quick level change.