44

Capacitive electrodes EL - Profibus PA

Sensor parameter adjustment – Sensor
optimisation

In this window, the mode of the sensor can
be set. With this, you modify the phase angle
of the phase selective admittance processing
(PSA). "Mode 1" is preset.

Mode 1 = Phase angle 90°

Mode 1 is a pure capacitance measurement,
the ohmic resistance is not taken into account
in the measuring result.
Application:
- standard adjustment
- non-conductive liquids up to approx. 50 µS
- compensation of conductance changes in

liquids

- generally with partly insulated electrodes in

liquids

- non-conductive solids without moisture

content

- with insufficient product grounding
- for electrodes in conjunction with a concen-

tric tube

- in non-conductive vessels with exterior

grounding plate outside

Mode 2 = Phase angle 45°

The capacitance and the ohmic conductance
are measured separately, the capacitance
value is corrected by calculating it with the
ohmic conductance, so that measuring errors
caused by conductive buildup or changes of
moisture content can be compensated.
Application:
- highly conductive products
- adhesive, conductive products
- solids with fluctuating moisture content

Setup

In the window "Profibus output" you can de-
termine the options for Profibus output (acc.
to Profibus PA instrument profile). Confirm the
settings with

OK

. The values under

"Scaling"

change the Profibus output and the value on
any display that may be connected. To use
the values for a display, "scaled" must be
chosen under "Display of measured value".

Click in the window "Outputs" to

Profibus

output

.

When clicking "Display of measured value",
you can choose twhat should be displayed
on the sensor display, e.g. level, capacitance
or scaled value.