Capacitive electrodes EL - Profibus PA

Setup

If you have chosen pF, you can assign a
corresponding value in Picofarad to the per-
centage value.
Example
0 % = 97.2 pF
100 % = 1428.0 pF

The values for the adjustment will be ac-
cepted by pushing the button

OK.

Conditioning

The following functions are available in this
window:
- Scaling
- Linearisation
- Integration time

Scaling

With this button, a message appears telling
you that for Profibus sensors, this function
can be found in the menu window "

Instrument

data parameter adjustment" under the menu
item "

Output". Carry out the scaling there.

Linearisation

In this window, you can linearise non-linear
vessels, such as e.g. a cylindrical tank. The
following linearisation curves are available:
- linear
- cylindrical tank
- spherical tank
- user-programmable curve

Click in the window "Instrument data param-
eter adjustment" to

Conditioning

.

Click in the window "Conditioning" to

Linearisation

.

With oscillator CAP E34 PA Ex you can also
enter your own linearisation curve for special
vessels, e.g. cylindrical vessel with large
funnel-shaped outlet, under "user-program-
mable curve".

Push the button

Edit. You can enter the value

pairs (percentage value - volume value) for
32 index markers.