Capacitive electrodes EL - Profibus PA

27

Electrical connection

Connection example for installation of an Ex system on vessels with cathodic cor-
rosion protection

The following overvoltage arrester can be used:
----- B62-30 W:

B62-30 W:

B62-30 W:

B62-30 W:

B62-30 W: 9 … 36 V DC, max. 1 A

B

A

2
1

E2
E1

A2
A1

B62-30 W

E2
E1

A2
A1

B62-30 W

Ex area, Zone 1 or Zone 2

Oscillator

Transmitter

External
ground terminal

Sensor

Screen

Overvoltage-
arrester
in metal or
plastic housing

Screen

Non-Ex area

Switching cabinet/Control room

Signal
condition-
ing
instrument
or
safety
barrier

optionally overvoltage
arrester

Vessel
Zone 0

Cathodic tank protection
2 … 24 V (object voltage)

Insulated cable min.
4 mm

2

Cu

A

A cable with either metal cover, screening or metallic protection tube according to VDE must be used
between overvoltage arrester and transmitter (metal cover, screening or protective tube must not be
grounded).
Test voltage of the cable "A"

1500 V AC.

B

A cable acc. to VDE, if necessary with metal cover or screen, must be used between control room and
overvoltage arrester. Metal cover or screen - if necessary - must only be connected on the transmitter
side of the overvoltage arrester. The cable must have an outer insulation.
Test voltage of the cable "B" ³ 500 V AC.