VEGA VEGASWING 83 fail safe and signal conditioning instrument VEGATOR 526 Ex User Manual
Page 9
VEGASWING 81 W5 Ex.C, 83 W5 Ex.C fail safe
9
Signal conditioning instrument VEGATOR 526 Ex
General
Series
module unit for carrier BGT 596 Ex
Dimensions
W = 50,8 mm (10 TE), H = 128,4 mm, D = 162 mm
Weight
approx. 440 g
Ambient conditions
Ambient temperature
-20
°
C … +60
°
C
Storage and transport temperature
-40
°
C … +70
°
C
Power supply
Operating voltage
U
N
= 24 V AC (20 … 28 V AC); 50/60 Hz
U
N
= 24 V DC (16 … 60 V DC
Power consumption
approx. 11 VA or 8 W
Electrical connection
multipoint connector DIN 41 612,
series F (d, z) 32-pole
Electrical protective measures
Protection class
II (in housing type 589-10 Ex)
Overvoltage category
II
Protection
- mounted in housing type 589…
IP 30
Protection
(mounted into carrier
BGT 596 Ex with Ex-module)
- front side (completely equipped)
IP 30
- upper and lower side
IP 20
- wiring side
IP 00
Inputs
Number
1
Data transmission
analogue, 4 … 20 mA
Current limitation
24 mA (permanently shortcircuit proof)
Sensor supply voltage
approx. 15 … 18 V DC
Connection line
2-wire (screened)
Resistance per conductor
max. 35
Ω
Function
Integration time
- switch on delay
0,5 s
- switch off delay
1,0 s
Product description