VEGASWING 81 W5 Ex.C, 83 W5 Ex.C fail safe

In case of products with deviating density, this
switch point shifts dependent on the density
and the installation to the direction of the
housing or tuning fork end (see following
table).

A density change by 0,1␣ g/cm

3

effects e.g. a

shifting of the switch point by approx. 2,5␣ mm.

To avoid faulty switching by probable
adhesions, the slide switch (7) must be set to
position 2 in case of adhesive, high viscosity
products.

By means of the slide switch (7) you can also
detect products below 1␣ g/cm

3

(0,5␣ …␣ 0,85␣ g/

cm

3

). In this case choose position 3. The

switch point is then again at the height of the
marking (25␣ mm above the tip of the fork).-

Note

- Modifications in the switch position are only

effective after the next voltage change-over.

- Modifications can be carried out any time

after the set-up.

Control lamps

LED in the front plate show on/off, switch
condition and failure.

Green

- mains control lamp (5)
- mains voltage on, instrument in operation

Red

- signal lamp (4)
- failure on the sensor circuit by failure of the

sensor of line defect.

- when the fail safe relay is de-energized, the

red signal lamp lights.

Set-up

Pre-adjustments

Before connecting VEGATOR 526␣ Ex to
voltage supply, the mode of the meas. system
and the sensitivity of the sensor must be
adjusted. The adjustment elements are on the
board of the signal conditioning instrument.

Mode

Mode A or B can be adjusted by means of the
hook switch (6).

Mode A (fail safe)

means with covered vibrating element
- Relay de-energizes
- LED-relay output lights
means with uncovered vibrating element
- Relay energizes
- LED-relay output extinguishes

Mode B (not fail safe)

means with covered vibrating element
- Relay energizes
- LED-relay output extinguishes
means with uncovered vibrating element
- Relay de-energizes
- LED-relay output lights

Density of the product

With the slide switch (7) you can modify the
sensitivity of the meas. system. Note that the
switch is never in position 1.

Position 3 - Density of the product

0,5␣ …␣ 0,85␣ g/cm

3

Position 2 - Density of the product

>␣ 0,85␣ g/cm

3

Position 1 - not allowed

The information on the position of the switch
point (see “2 Mounting“) relates to water in
conjunction with the slide switch on position 2.