VEGASWING 81 W5 Ex.C, 83 W5 Ex.C fail safe

27

Failure

Reason / Removal

After pushing the
set-up key (3)

- set-up was carried out with covered tuning fork.

Carry out a new start and repeat the set-up with uncovered
tuning fork.

- set-up key was pushed too long (>␣ 6␣ s)

Carry out a new start and repeat the set-up. Note the correct
period for pushing the set-up key (3).

During operation

Check the following reasons:
- line break
- short-circuit
- electronics defect

In case of an electronics defect, call our service department.

Diagnosis

VEGATOR 526 Ex

on

lights

off

lights

lights for
approx. 2 s

VEGATOR 526 Ex

on

lights

leuchtet

leuchtet

aus