VEGASWING 81 W5 Ex.C, 83 W5 Ex.C fail safe

21

Electrical connection

E2

E1

A2

A1

A1

A2

E2

E1

1
2

Typ

B62-27

Typ

B62-27G

d30

d32

E86 Ex

Overvoltage
arrester

min. 4 mm

2

Cu

Screen

optionally
overvoltage arrester

Note:

- Use suitable cable, optionally with metal cover or screen. Screen or metal cover must only be

connected to the overvoltage arrester. Screen or metal cover must not be earthed.

- The cable must have an outer isolation.
- The capacity of the screen must at least correspond to that of a 1,5 mm

2

Cu-line.

Earth / PA
connection terminal

Outer
isolation

Vessel with cathodic corrosion protection

Screen

Line length

␣ 50 m

Metal housing
isolated mounted or
plastic housing

Overvoltage arrester
type B62 - 27 Ex 0
or B62 - 27 Ex

Outer
isolation

External
earth
terminal

Cathodic tank protection
2 … 24 V
(object voltage)

VEGASWING

VEGATOR
526 Ex

Ex-area

Not Ex-area
(control room)