Technical data

6 Technical data

6.1 Technical data

Power supply

Supply voltage

9 … 32 V DC

(output voltage U

O

of the segment

(depending on segment coupler used)

coupler)

see PA specification, e.g.

- non-Ex

22 V DC (nominal voltage of the segment
coupler) max. 32 sensors on one two-wire
cable

- Ex

13.5 V DC (nominal voltage of the segment
coupler) max. 10 sensors on one two-wire
cable (typically 8 sensors)

Current consumption

constantly 10 mA (no leakage current output)

Load

depending on segment coupler, see
technical data of the segment couplers and
Profibus specification

Measuring range

VEGAFLEX 54

rod 0.15 ... 4 m (with DK value > 4: 0.1 … 4 m)
cable 0.15 … 20 m
(with DK value < 4: 0.3 … 20 m)

Output signal

digital (Profibus)

Two-wire technology:

The digital output signal (measuring signal) is
modulated onto the power supply and further
processed in the PLC or process control room .

Integration time

0 … 999 seconds (adjustable)

Adjustment

- adjustment software VEGA Visual Operating on Master-Class 2 PC
- adjustment module MINICOM in the sensor or in the external instrument (optional)
- process adjustment interface PACTware

TM

(under which VVO runs as a subprogram)

- SIMATIC PDM in conjunction with Electronic Device Description (EDD)

Accuracy

1)

(under reference conditions acc. to IEC 770 - relating to the max. measuring range)

Linearity error

< 0.1 %

Temperature drift

0.015 %/10 K

Characteristics

linear

Deviation in characteristics incl.

linearity, reproducibility and
hysteresis (limit point method)

better than 0.05 %

Average temperature coefficient of the
zero signal

0.06 %/10 K

General resolution

max. 1 mm

Resolution of the output signal

0.005 % or 1 mm

1)

Similar to DIN 16 086, reference conditions acc. to IEC 770, e.g.
temperature 15°C … 35°C; moisture 45 % … 75 %; pressure 860 mbar … 1060 mbar