beautypg.com

3 adjustment with the pc – VEGA VEGAFLEX 54P (Profibus PA) User Manual

Page 32

background image

32

VEGAFLEX 54P (Profibus PA)

Setup

VEGA signal condit. instrument

Rx

VEGAMET 513, 514, 515, 602

50 … 100 Ohm

VEGAMET 614

no additional

VEGADIS 371

resistance
necessary

VEGAMET 601

200 … 250 Ohm

VEGASEL 643

150 … 200 Ohm

VEGAMET 513 S4, 514 S4
515 S4, VEGALOG EA card

100 … 150 Ohm

4.3 Adjustment with the PC

The adjustment with the PC and the adjust-
ment program VVO is not described in this
operating instructions manual, but in the
manual "VEGA Visual Operating (VVO)“.
Beside the adjustment of VEGAFLEX, you will
find in the manual VEGA Visual Operating
further information on the scope of the adjust-
ment options with the PC.

If you operate a sensor in conjunction with a
VEGA signal conditioning instrument, please
use an additional communication resistor acc.
to the following table:

Before you can set up the sensors with the
adjustment program VVO (VEGA Visual
Operating), they have to be integrated into
the Profibus system. First of all, address the
sensors and connect them to your PA seg-
ment. With the attached GSD file, you inte-
grate the sensors into your system.

To set up VEGA sensors with the adjustment
software VVO, the PC or the adjustment
station on which VVO is installed must be
equipped with a Profibus DP interface card
(e.g. from Softing). The PC or adjustment
station then communicates as Master-Class 2
participant on the DP bus with the VEGA
sensors on the PA bus segment.

Sensor

Sensor

Sensor

Sensor

VVO

Segment
coupler

Profibus PA
cable

Profibus DP-
interface card
(Messrs. Softing)

DP cable

To connect the PC to the DP bus a standard
RS 485-DTE interface cable (Data Terminal
equipment) is required. With the cable, you
connect the DP interface card to the bus or
the segment coupler.

PC

PC

PC

PC

PC

BUS

BUS

BUS

BUS

BUS

Screen

1

1 Screen

– –

2

2 M24

RxD/TxD-P

RxD/TxD-P

RxD/TxD-P

RxD/TxD-P

RxD/TxD-P

3

3

3

3

3

3

3

3

3

3 RxD/TxD-P

RxD/TxD-P

RxD/TxD-P

RxD/TxD-P

RxD/TxD-P

(40)

– –

4

4 CNTR-P

GND

GND

GND

GND

GND

5

5

5

5

5

5

5

5

5

5 GND

GND

GND

GND

GND

(55)

– –

6

6 VP

– –

7

7 P24

RxD/TxD-N

RxD/TxD-N

RxD/TxD-N

RxD/TxD-N

RxD/TxD-N

8

8

8

8

8

8

8

8

8

8 RxD/TxD-N

RxD/TxD-N

RxD/TxD-N

RxD/TxD-N

RxD/TxD-N

(41)

– –

9

9 CNTR-P

Profibus-DP

DP bus (in brackets the

interface card

PIN number of the P+F
segment couplers)

After having connected the computer to the
Profibus DP cable, VVO can be started.