beautypg.com

Software addressing – VEGA VEGAFLEX 54P (Profibus PA) User Manual

Page 22

background image

22

VEGAFLEX 54P (Profibus PA)

Electrical connection

Example 2

You want to set address 27.
16 + 8 + 2 + 1 = 27

You must set the DIP switches
5 = 16
4 = 8
2 = 2
1 = 1
to "ON“.

Example 3

You want to set address 99
64 + 32 + 2 + 1 = 99

You must set the DIP switches
7 = 64
6 = 32
2 = 2
1 = 1
to "ON“.

Software addressing

The DIP switches must be set to an address
of 126 … 255, i.e.

- either all DIP switches are set to "ON“,

corresponding to address 255 (delivery
status)

ON

Addr.

8 7 6 5 4 3 2 1

OFF

1

2

4

8

16

32

64

128

8 7 6 5 4 3 2 1

- or only DIP switch 8 is set to "ON“, corre-

sponding to address 128.

Of course, software addressing is also pos-
sible if the switches 7 … 2 are set to "ON“
(address 126).

The adjustment of the address with software
VVO is described in the operating instruc-
tions manual of the adjustment software VVO.

The address adjustment can also be carried
out with the adjustment module MINICOM.
Note the menu schematics of MINICOM.