beautypg.com

7 approvals, 8 data format of the output signal – VEGA VEGAFLEX 54P (Profibus PA) User Manual

Page 14

background image

14

VEGAFLEX 54P (Profibus PA)

Product description

1.7 Approvals

VEGAFLEX sensors are approved for StEx Zone 10.

Observe the attached approval documents when using a sensor in Ex environment.

1.8 Data format of the output signal

Byte4

Byte3

Byte2

Byte1

Byte0

Status

Measured value (IEEE-754 Format, see below)

Status byte:

The status byte corresponds to profile 3,0 "Profibus PA Profile for Process Control Devices“
coded. The status "Measured value OK“ is coded as 80 (hex) (Bit7 = 1, Bit 6 … 0 = 0).

Measured value:

The measured value is transmitted as a 32 Bit floating point number in IEEE-754 format.

Byte n

Byte n+1

Bit

Bit

Bit

Bit

Bit

Bit

Bit

Bit

Bit

Bit

Bit

Bit

Bit

Bit

Bit

Bit

7

6

5

4

3

2

1

0

7

6

5

4

3

2

1

0

VZ

2

7

2

6

2

5

2

4

2

3

2

2

2

1

2

0

2

-1

2

-2

2

-3

2

-4

2

-5

2

-6

2

-7

Sign

Exponent

Mantissa

Byte n+2

Byte n+3

Bit

Bit

Bit

Bit

Bit

Bit

Bit

Bit

Bit

Bit

Bit

Bit

Bit

Bit

Bit

Bit

7

6

5

4

3

2

1

0

7

6

5

4

3

2

1

0

2

-8

2

-9

2

-10

2

-11

2

-12

2

-13

2

-14

2

-15

2

-16

2

-17

2

-18

2

-19

2

-20

2

-21

2

-22

2

-23

Mantissa

Mantissa

Formula:

Measured value = (-1)

VZ

• 2

(Exponent - 127)

• (1 + Mantissa)

Examples:

41 70 00 00 (hex) = 0100 0001 0111 0000 0000 0000 0000 0000 (bin)
Meas. value

= (-1)

0

• 2

(130 - 127)

• (1 + 2

-1

+ 2

-2

+ 2

-3

)

= 1 • 2

3

• (1 + 0.5 + 0.25 + 0.125)

= 1 • 8 • 1.875
= 15.0