7 approvals, 8 data format of the output signal – VEGA VEGAFLEX 54P (Profibus PA) User Manual
Page 14
14
VEGAFLEX 54P (Profibus PA)
Product description
1.7 Approvals
VEGAFLEX sensors are approved for StEx Zone 10.
Observe the attached approval documents when using a sensor in Ex environment.
1.8 Data format of the output signal
Byte4
Byte3
Byte2
Byte1
Byte0
Status
Measured value (IEEE-754 Format, see below)
Status byte:
The status byte corresponds to profile 3,0 "Profibus PA Profile for Process Control Devices“
coded. The status "Measured value OK“ is coded as 80 (hex) (Bit7 = 1, Bit 6 … 0 = 0).
Measured value:
The measured value is transmitted as a 32 Bit floating point number in IEEE-754 format.
Byte n
Byte n+1
Bit
Bit
Bit
Bit
Bit
Bit
Bit
Bit
Bit
Bit
Bit
Bit
Bit
Bit
Bit
Bit
7
6
5
4
3
2
1
0
7
6
5
4
3
2
1
0
VZ
2
7
2
6
2
5
2
4
2
3
2
2
2
1
2
0
2
-1
2
-2
2
-3
2
-4
2
-5
2
-6
2
-7
Sign
Exponent
Mantissa
Byte n+2
Byte n+3
Bit
Bit
Bit
Bit
Bit
Bit
Bit
Bit
Bit
Bit
Bit
Bit
Bit
Bit
Bit
Bit
7
6
5
4
3
2
1
0
7
6
5
4
3
2
1
0
2
-8
2
-9
2
-10
2
-11
2
-12
2
-13
2
-14
2
-15
2
-16
2
-17
2
-18
2
-19
2
-20
2
-21
2
-22
2
-23
Mantissa
Mantissa
Formula:
Measured value = (-1)
VZ
• 2
(Exponent - 127)
• (1 + Mantissa)
Examples:
41 70 00 00 (hex) = 0100 0001 0111 0000 0000 0000 0000 0000 (bin)
Meas. value
= (-1)
0
• 2
(130 - 127)
• (1 + 2
-1
+ 2
-2
+ 2
-3
)
= 1 • 2
3
• (1 + 0.5 + 0.25 + 0.125)
= 1 • 8 • 1.875
= 15.0