Mounting

Measuring range

The electrode (rod / cable) cannot be used
over its entire length.
Keep especially in mind that the cable length
cannot be utilised down to the very tip. A
measurement in the area of the gravity weight
is not possible.
Rod 0.15 ... 4 m (with DK value > 4: 0.1 … 4 m)
Cable 0.15 … 20 m (with DK value < 4:
0.3 … 20 m)

0%

100%

x

L

0%

100%

x

L

Measuring range

Sockets

Avoid long sockets. Mount the sensor flush
and use short sockets with small diameters.
Note under "4.3 Adjustment with PC/Empty
vessel profile".

If VEGAFLEX is mounted on a socket or
mounting boss, the measurement at close
range can be inaccurate. If your socket or
mounting boss exceeds the following
lengths, a storage of the empty vessel profile
should be carried out.

Thread 1“, 1

1

/

2

- Length > 50 mm

Flange DN 50

- Length > 50 mm

Flange DN 80

- Length > 80 mm

Flange

DN 100

- Length > 100 mm