beautypg.com

Section 4. remote operation, Introduction, Remote digital programming – Xantrex Technology XPD 60-9 User Manual

Page 51: Figure 4.1 j210 user cable with ferrite block, Section 4, Remote, Operation, Section 4. remote operation, Remote operation

background image

Release A

49

Section 4. Remote Operation

Introduction

The switches and connector on the rear panel of the power supply allow you to
program the supply with an analog device or to readback analog signals.

Remote

Digital

Programming

You can operate the power supply from a computer if you have the optional GPIB or
RS-232 interface card installed. Refer to the separate interface manual for all setup
and operation instructions for remote digital programming.

Remote Analog Programming of Output Voltage and Current Limit

Remote analog programming allows control of the power supply’s output voltage
and output current limit to shift from local operation at the front panel voltage and
current controls to external analog input sources. As you vary the programming
source, the power supply’s output varies proportionally over its output range.

Using remote analog programming requires that you make connections to the J210
connector on the power supply’s rear panel. See

“Rear Panel J210 Connector” on

page 15

. To reduce radiated emissions, add a ferrite block to the wires that go to the

J210 connector. The 1 inch square ferrite block with built in housing clip is packaged
and shipped with the power supply.

Figure 4.1 J210 User Cable with Ferrite Block

J210 cable

Ferrite Block

To user interface

J210 connector

Max. 5 cm