beautypg.com

York YR User Manual

Page 23

background image

23

YORK INTERNATIONAL

FORM 160.81-EG1

FLA

=

Motor kW

x

Max. Motor FLA

Max. Motor kW

The benefit from the FLA correction is the possible use
of smaller power wiring and/or starter size.

The locked rotor amperes (LRA) are read directly from
Tables 3 and 4 for specific Motor Code and voltage. This
is because the LRA is dependent only on motor size and
voltage and is independent of input power (kW).

Inrush amperes (IRA) depend on LRA and the type of
starter applied. The inrush can be calculated using a
percentage of LRA shown in Table 5.

TABLE 3 – 60 HZ ELECTRICAL DATA

NAME- AMP

MOTOR DATA

COMP. PLATE

(MAX)

100%

90%

80%

70%

60%

50%

40%

30%

20%

MAX.

VOLT. FLA LRA

PF

EFF

PF

EFF

PF

EFF PF EFF PF

EFF

PF

EFF

PF EFF

PF

EFF

PF EFF

KW (hp)

200

850 3634

88.2

94.8

87.8

95.2 87.3 95.5 85.8 95.7 84.3 95.9 80.4 96.0 76.5 96.0 65.8 95.2 55.1 94.4

208

825 3779

86.6

95.0

85.6

95.3 84.6 95.5 82.6 95.7 80.5 95.9 75.5 95.8 70.5 95.7 59.0 94.8 47.4 93.8

230

725 2901

89.2

94.5

89.1

95.0 89.0 95.4 88.2 95.7 87.3 96.0 84.5 96.1 81.6 96.2 72.4 95.6 63.1 94.9

240

695 3027

88.2

94.9

87.7

95.2 87.2 95.5 85.8 95.8 84.3 96.0 80.4 96.0 76.5 96.0 65.8 95.2 55.0 94.4

T0/T1

380

438 1727

89.3

94.6

89.3

95.0 89.2 95.4 88.5 95.7 87.8 96.0 85.1 96.1 82.4 96.2 73.5 95.6 64.6 95.0

251.6

440

370 1390

89.6

94.2

89.8

94.7 90.0 95.2 89.6 95.6 89.2 95.9 87.2 96.1 85.2 96.3 77.7 95.9 70.1 95.4

(321)

460

354 1453

89.2

94.6

89.1

95.0 88.9 95.4 88.1 95.7 87.3 96.0 84.5 96.1 81.6 96.2 72.4 95.6 63.1 94.9

480

339 1516

88.2

94.9

87.7

95.2 87.2 95.5 85.8 95.8 84.3 96.0 80.4 96.0 76.5 96.0 65.8 95.2 55.0 94.4

575

300 1162

89.2

94.6

89.1

95.0 88.9 95.4 88.1 95.7 87.3 96.0 84.4 96.1 81.5 96.2 72.3 95.6 93.1 95.0

600

288 1213

88.2

94.9

87.7

95.3 87.2 95.6 85.8 95.8 84.3 96.0 80.4 96.0 76.5 96.0 65.8 95.3 55.0 94.5

200

882 4048

90.4

94.8

90.2

95.2 90.0 95.5 89.2 95.8 88.3 96.0 85.6 96.0 82.9 96.0 73.8 95.3 64.7 94.6

208

860 4210

89.1

95.0

88.5

95.3 87.8 95.6 86.4 95.8 94.9 96.0 81.3 96.0 77.6 95.9 67.1 95.0 56.5 94.1

230

760 3520

90.5

94.7

90.4

95.1 90.2 95.4 89.5 95.7 88.7 95.9 86.2 96.0 83.7 96.0 75.0 95.4 66.3 94.7

240

737 3673

89.3

95.0

88.8

95.3 88.3 95.5 86.9 95.7 85.4 95.9 81.9 95.9 78.3 95.9 67.9 95.0 57.5 94.1

T2/T3

380

464 2130

90.3

94.8

90.1

95.2 89.9 95.5 89.1 95.8 88.2 96.0 85.6 96.0 82.9 96.0 73.8 95.3 64.7 94.6

275.9

440

400 1603

91.0

94.4

91.2

94.9 91.4 95.3 91.1 95.6 90.8 95.9 89.3 96.1 87.7 96.2 80.9 95.7 74.0 95.1

(351)

460

383 1676

90.5

94.7

90.4

95.1 90.2 95.5 89.5 95.8 88.7 96.0 86.2 96.1 83.7 96.1 75.0 95.4 66.2 94.7

480

372 1749

89.3

95.0

88.8

95.3 88.2 95.6 86.8 95.8 85.4 96.0 81.8 96.0 78.2 95.9 67.9 95.0 57.5 94.1

575

305 1408

90.7

94.7

90.7

95.1 90.6 95.5 90.0 95.8 89.4 96.0 87.2 96.1 85.0 96.2 77.0 95.5 68.9 94.8

600

293 1469

89.9

95.0

89.5

95.3 89.1 95.6 88.0 95.8 86.9 96.0 83.8 96.0 80.7 96.0 71.0 95.2 61.2 94.4

NOTE: FLA = Full-load Amps; LRA = Locked Rotor Amps; PF = Power Factor; EFF = Motor Efficiency

100% Loading is Percentage of Maximum Motor Load; not of Specific Application