beautypg.com

York PREDATOR BP120 User Manual

Page 40

background image

66307-YIM-B-0606

40

Unitary Products Group

FIGURE 24: UNIT CONTROL BOARD

TABLE 38: UNIT CONTROL BOARD FLASH CODES

FLASH CODE

DESCRIPTION

GREEN

LED

16

RED

LED

8

RED

LED

4

RED

LED

2

RED

LED

1

On Steady

This is a Control Failure

-

-

-

-

-

1 Flash

Not Applicable

-

-

-

-

-

2 Flashes

Control waiting ASCD

*

Flashing

Off

Off

On

Off

3 Flashes

HPS1 Compressor Lockout

Off

Off

Off

On

On

4 Flashes

HPS2 Compressor Lockout

Off

Off

On

Off

Off

5 Flashes

LPS1 Compressor Lockout

Off

Off

On

Off

On

6 Flashes

LPS2 Compressor Lockout

Off

Off

On

On

Off

7 Flashes

FS1 Compressor Lockout

Off

Off

On

On

On

8 Flashes

FS2 Compressor Lockout

Off

On

Off

Off

Off

9 Flashes

Ignition Control Locked Out / Ignition Control Failure

Off

On

Off

Off

On

10 Flashes

Compressors Locked Out on Low Outdoor Air Temperature

1

Flashing

On

Off

On

Off

11 Flashes

Compressors locked out because the Economizer is using free

Cooling

1

Flashing

On

Off

On

On

12 Flashes

Unit Locked Out due to Fan Overload Switch Failure

Off

On

On

Off

Off

13 Flashes

Compressor Held Off due to Low Voltage

1

Flashing

On

On

Off

On

14 Flashes

EEPROM Storage Failure

Off

On

On

On

Off

OFF

No Power or Control Failure

Off

Off

Off

Off

Off

*.

Non-alarm condition.

Check

Alarm

History

Reset All

ASCDs for
One Cycle

Non Alarm

Condition Green

LED Flashing

Current Alarm

Flashed

Red LED