York PREDATOR BP120 User Manual
Page 40
66307-YIM-B-0606
40
Unitary Products Group
FIGURE 24: UNIT CONTROL BOARD
TABLE 38: UNIT CONTROL BOARD FLASH CODES
FLASH CODE
DESCRIPTION
GREEN
LED
16
RED
LED
8
RED
LED
4
RED
LED
2
RED
LED
1
On Steady
This is a Control Failure
-
-
-
-
-
1 Flash
Not Applicable
-
-
-
-
-
2 Flashes
Control waiting ASCD
*
Flashing
Off
Off
On
Off
3 Flashes
HPS1 Compressor Lockout
Off
Off
Off
On
On
4 Flashes
HPS2 Compressor Lockout
Off
Off
On
Off
Off
5 Flashes
LPS1 Compressor Lockout
Off
Off
On
Off
On
6 Flashes
LPS2 Compressor Lockout
Off
Off
On
On
Off
7 Flashes
FS1 Compressor Lockout
Off
Off
On
On
On
8 Flashes
FS2 Compressor Lockout
Off
On
Off
Off
Off
9 Flashes
Ignition Control Locked Out / Ignition Control Failure
Off
On
Off
Off
On
10 Flashes
Compressors Locked Out on Low Outdoor Air Temperature
1
Flashing
On
Off
On
Off
11 Flashes
Compressors locked out because the Economizer is using free
Cooling
1
Flashing
On
Off
On
On
12 Flashes
Unit Locked Out due to Fan Overload Switch Failure
Off
On
On
Off
Off
13 Flashes
Compressor Held Off due to Low Voltage
1
Flashing
On
On
Off
On
14 Flashes
EEPROM Storage Failure
Off
On
On
On
Off
OFF
No Power or Control Failure
Off
Off
Off
Off
Off
*.
Non-alarm condition.
Check
Alarm
History
Reset All
ASCDs for
One Cycle
Non Alarm
Condition Green
LED Flashing
Current Alarm
Flashed
Red LED