66307-YIM-B-0606

Unitary Products Group

11

CLEARANCES

All units require particular clearances for proper operation
and service. Refer to Table 6 for clearances required for con-
struction, servicing, and proper unit operation.

NOTE:

A one-inch clearance must be provided between
any combustible material and the supply ductwork
for a distance of 3 feet from the unit.

Do not permit overhanging structures or shrubs to
obstruct condenser air discharge outlet, combustion
air inlet or vent outlets.

FIGURE 8 -

UNIT DIMENSIONS

F o r B a s e r a i l

D i m e n s i o n s

S e e D e t a i l A

8 9

( 2 2 6 0 )

2 7

( 6 8 5 )

5 9

( 1 5 0 0 )

5 0 - 3 / 4

( 1 2 9 0 )

4 - 1 / 4

( 1 1 0 )

1 7 - 3 / 1 6

( 4 3 5 )

2 4 - 3 / 1 6

( 6 1 5 )

3 0 - 3 / 1 6

( 7 6 5 )

P o w e r

E n t r y

Ø 2 - 1 / 2

( 6 5 )

3 0 - 1 1 / 3 2

( 7 7 0 )

C o n t r o l

E n t r y

Ø 7 / 8

( 2 2 )

P o w e r

E n t r y

Ø 2 - 1 / 2

( 6 5 )

L E F T

F R O N T

6 - 3 / 1 6

( 1 5 5 )

C o n v e n i e n c e

P o w e r

O u t l e t

E n t r y

Ø 7 / 8

( 2 2 )

N O T E : ( x x x ) i n d i c a t e s d i m e n s i o n s

g i v e n i n m i l l i m e t e r s

F o r D r a i n

D i m e n s i o n s

S e e D e t a i l B

TABLE 6: UNIT CLEARANCES

*

*.

In inches and millimeters, in.(mm).

Top

†.

Units must be installed outdoors. Overhanging structure or
shrubs should not obstruct condenser air discharge outlet.

72 (1830)

Right

12 (305)

Front

36 (915)

Left

36 (915)

Rear

‡.

To remove the slide-out drain pan, a rear clearance of 60”
(1525 mm) is required. If space is unavailable, the drain pan
can be removed through the front by separating the corner
wall.

36 (915)

Bottom

**

**.

Units may be installed on combustible floors.

0 (0)

3 - 3 / 4

( 9 5 )

3 - 9 / 1 6

( 9 0 )

2 - 3 / 8

( 6 0 )

DETAIL A

5 - 3 / 8

( 1 3 5 )

DETAIL B