Clearances, Figure 8 - unit dimensions, Table 6: unit clearances – York PREDATOR BP120 User Manual
Page 11: Detail a, Detail b
66307-YIM-B-0606
Unitary Products Group
11
CLEARANCES
All units require particular clearances for proper operation
and service. Refer to Table 6 for clearances required for con-
struction, servicing, and proper unit operation.
NOTE:
A one-inch clearance must be provided between
any combustible material and the supply ductwork
for a distance of 3 feet from the unit.
Do not permit overhanging structures or shrubs to
obstruct condenser air discharge outlet, combustion
air inlet or vent outlets.
FIGURE 8 -
UNIT DIMENSIONS
F o r B a s e r a i l
D i m e n s i o n s
S e e D e t a i l A
8 9
( 2 2 6 0 )
2 7
( 6 8 5 )
5 9
( 1 5 0 0 )
5 0 - 3 / 4
( 1 2 9 0 )
4 - 1 / 4
( 1 1 0 )
1 7 - 3 / 1 6
( 4 3 5 )
2 4 - 3 / 1 6
( 6 1 5 )
3 0 - 3 / 1 6
( 7 6 5 )
P o w e r
E n t r y
Ø 2 - 1 / 2
( 6 5 )
3 0 - 1 1 / 3 2
( 7 7 0 )
C o n t r o l
E n t r y
Ø 7 / 8
( 2 2 )
P o w e r
E n t r y
Ø 2 - 1 / 2
( 6 5 )
L E F T
F R O N T
6 - 3 / 1 6
( 1 5 5 )
C o n v e n i e n c e
P o w e r
O u t l e t
E n t r y
Ø 7 / 8
( 2 2 )
N O T E : ( x x x ) i n d i c a t e s d i m e n s i o n s
g i v e n i n m i l l i m e t e r s
F o r D r a i n
D i m e n s i o n s
S e e D e t a i l B
TABLE 6: UNIT CLEARANCES
*
*.
In inches and millimeters, in.(mm).
Top
†
†.
Units must be installed outdoors. Overhanging structure or
shrubs should not obstruct condenser air discharge outlet.
72 (1830)
Right
12 (305)
Front
36 (915)
Left
36 (915)
Rear
‡
‡.
To remove the slide-out drain pan, a rear clearance of 60”
(1525 mm) is required. If space is unavailable, the drain pan
can be removed through the front by separating the corner
wall.
36 (915)
Bottom
**
**.
Units may be installed on combustible floors.
0 (0)