York PREDATOR BP120 User Manual
Page 32
66307-YIM-B-0606
32
Unitary Products Group
TABLE 30: ADDITIONAL STATIC RESISTANCE - IMPERIAL
CFM
Cooling Only
*
Economizer
†
‡
Electric Heat KW
†
9
18
24
36
54
2300
0.08
0.02
0.07
0.08
0.09
0.10
0.13
2500
0.09
0.02
0.08
0.09
0.10
0.11
0.14
2700
0.11
0.03
0.09
0.10
0.12
0.13
0.16
2900
0.12
0.03
0.10
0.11
0.13
0.14
0.18
3100
0.14
0.03
0.12
0.13
0.15
0.16
0.20
3300
0.16
0.03
0.13
0.14
0.17
0.18
0.22
3500
0.18
0.04
0.15
0.16
0.19
0.20
0.24
3700
0.20
0.04
0.17
0.18
0.21
0.22
0.26
3900
0.23
0.04
0.19
0.20
0.23
0.24
0.28
4100
0.25
0.04
0.21
0.22
0.25
0.26
0.31
4300
0.28
0.05
0.23
0.24
0.28
0.29
0.34
4500
0.30
0.05
0.25
0.26
0.30
0.31
0.37
4700
0.33
0.05
0.28
0.29
0.33
0.34
0.40
4900
0.36
0.05
0.30
0.31
0.35
0.37
0.43
5100
0.39
0.06
0.33
0.34
0.38
0.40
0.46
5300
0.42
0.06
0.35
0.37
0.41
0.43
0.49
*.
Add these resistance values to the available static resistance in the respective Blower Performance Tables.
†.
Deduct these resistance values from the available external static pressure shown in the respective Blower Performance Table.
‡.
The pressure drop through the economizer is greater for 100% outdoor air than for 100% return air. If the resistance of the return
air duct system is less than 0.25 IWG, the unit will deliver less CFM during full economizer operation.
TABLE 31: ADDITIONAL STATIC RESISTANCE - METRIC
M
3
S
Cooling Only
*
Economizer
†
‡
Electric Heat KW
†
9
18
24
36
54
1.08
19.9
5.0
17.4
19.9
22.4
24.8
32.3
1.18
22.4
5.0
19.9
22.4
24.8
27.3
34.8
1.27
27.3
7.5
22.4
24.8
29.8
32.3
39.7
1.36
29.8
7.5
24.8
27.3
32.3
34.8
44.7
1.46
34.8
7.5
29.8
32.3
37.3
39.7
49.7
1.55
39.7
7.5
32.3
34.8
42.2
44.7
54.6
1.65
44.7
9.9
37.3
39.7
47.2
49.7
59.6
1.74
49.7
9.9
42.2
44.7
52.2
49.7
64.6
1.83
57.1
9.9
47.2
49.7
56.1
59.6
69.5
1.93
62.1
9.9
52.2
54.6
62.1
64.6
77.0
2.02
69.5
12.4
57.1
59.6
69.5
72.0
88.4
2.12
74.5
12.4
62.1
64.6
74.5
77.0
91.9
2.21
82.0
12.4
69.5
72.0
82.0
84.4
99.3
2.30
89.4
12.4
74.5
77.0
86.9
91.9
106.8
2.40
96.9
14.9
82.0
84.4
94.4
99.3
114.2
2.49
104.3
14.9
86.9
91.9
101.8
106.8
121.7
*.
Add these resistance values to the available static resistance in the respective Blower Performance Tables.
†.
Deduct these resistance values from the available external static pressure shown in the respective Blower Performance Table.
‡.
The pressure drop through the economizer is greater for 100% outdoor air than for 100% return air. If the resistance of the return
air duct system is less than 0.25 IWG, the unit will deliver less CFM during full economizer operation.