York H*RA036 THRU 090 User Manual
Page 18
036-21121-002 Rev. A (0602)
18
Unitary Products Group
Multipliers for determining the performance with other indoor sections.
COOLING PERFORMANCE DATA
AIR CONDITIONER MODEL NO.
H1RA090S(25,46)
INDOOR COIL MODEL NO.
K4EV090
CONDENSER
ENTERING AIR
TEMPERATURE
ID CFM
2400
3000
3600
ID DB (°F)
85
80
70
85
80
70
85
80
70
ID WB (°F)
72
67
57
72
67
57
72
67
57
75
T.C.
104.2
97.2
90.1
108.1
100.5
92.8
112.1
103.8
95.5
S.C.
76.5
71.0
65.6
78.7
72.8
66.9
81.0
74.6
68.2
K.W
8.30
8.21
8.13
8.33
8.25
8.18
8.36
8.29
8.23
85
T.C.
99.1
92.4
85.8
102.0
94.7
87.5
104.8
97.0
89.1
S.C.
72.5
67.4
62.3
74.0
68.4
62.8
75.5
69.4
63.4
K.W
8.97
8.86
8.75
9.01
8.90
8.79
9.04
8.94
8.84
95
T.C.
94.0
87.7
81.5
95.8
89.0
82.1
97.5
90.1
82.7
S.C.
68.6
63.8
59.0
69.3
64.0
58.7
70.0
64.2
58.5
K.W
9.64
9.50
9.37
9.68
9.55
9.41
9.72
9.59
9.45
105
T.C.
88.2
82.2
76.1
89.8
83.9
77.9
91.4
85.6
79.7
S.C.
68.7
63.7
58.7
69.2
64.3
59.4
69.8
64.9
60.1
K.W
10.33
10.14
9.96
10.38
10.21
10.03
10.43
10.27
10.10
115
T.C.
82.5
76.6
70.8
83.9
78.8
73.8
85.3
81.0
76.7
S.C.
59.9
55.4
50.9
60.2
56.3
52.4
60.5
57.2
53.9
K.W
11.02
10.79
10.55
11.08
10.87
10.65
11.14
10.95
10.76
125
T.C.
76.7
71.1
65.5
78.0
73.8
69.6
79.2
76.5
73.7
S.C.
55.5
51.2
46.8
55.7
52.4
49.2
55.8
53.7
51.6
K.W
11.71
11.43
11.15
11.78
11.53
11.28
11.86
11.63
11.41
NOTE:
ALL CAPACITIES ARE NET WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH/1000 CFM.
Coil
T.C.
S.C.
KW
G2FD090S35
1.01
1.01
1.01