Multipliers for determining the performance with other indoor sections.
1 Phase
3 Phase
COOLING PERFORMANCE DATA
AIR CONDITIONER MODEL NO.
H1RA042S06, H1RA042S(25,46)
INDOOR COIL MODEL NO.
G1FA048S21,24
CONDENSER
ENTERING AIR
TEMPERATURE
ID CFM
1200
1400
1600
ID DB (°F)
85
80
70
85
80
70
85
80
70
ID WB (°F)
72
67
57
72
67
57
72
67
57
75
T.C.
47.2
44.1
41.2
47.5
44.6
41.9
47.9
45.1
42.6
S.C.
30.2
29.6
29.4
31.9
31.1
31.0
33.6
32.6
32.6
K.W
3.90
3.85
3.78
4.05
3.99
3.94
4.19
4.14
4.09
85
T.C.
45.5
42.1
38.5
45.9
42.8
39.3
46.3
43.4
40.2
S.C.
29.8
28.9
28.1
31.4
30.7
30.0
33.0
32.5
31.9
K.W
4.13
4.06
3.96
4.28
4.21
4.13
4.43
4.36
4.29
95
T.C.
43.9
40.2
35.7
44.3
41.0
36.8
44.8
41.8
37.8
S.C.
29.5
28.2
26.9
30.9
30.3
29.1
32.4
32.4
31.2
K.W
4.36
4.27
4.14
4.52
4.43
4.31
4.67
4.59
4.49
105
T.C.
40.5
36.3
32.0
41.2
37.1
32.8
42.0
38.0
33.7
S.C.
28.1
26.7
25.1
29.9
28.8
27.2
31.7
30.9
29.3
K.W
4.58
4.44
4.30
4.74
4.60
4.47
4.89
4.77
4.64
115
T.C.
37.1
32.3
28.3
38.2
33.3
28.9
39.2
34.2
29.6
S.C.
26.8
25.1
23.3
29.0
27.2
25.4
31.1
29.4
27.4
K.W
4.81
4.62
4.45
4.96
4.78
4.62
5.10
4.95
4.79
125
T.C.
33.7
28.4
24.5
35.1
29.4
25.0
36.4
30.4
25.4
S.C.
25.5
23.5
21.5
28.0
25.7
23.5
30.5
27.9
25.5
K.W
5.04
4.79
4.61
5.18
4.96
4.78
5.32
5.13
4.94
NOTE:
ALL CAPACITIES ARE NET WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH/1000 CFM.
Air Handler
Coil
T.C.
S.C.
KW
N1AHC1606
G2FD042S21
0.96
0.96
0.99
N1AHC1606
G2FD048S21
1.00
1.00
1.01
F2RP/F2FP042
0.96
0.95
0.99
F2FP048
0.99
0.99
0.99
G1FA048S17
0.98
1.00
1.00
G1FA060S21,24
1.02
1.02
1.00
G1HD048
0.99
0.99
1.01
G1NA036S21C
0.98
0.93
0.99
G1NA048S21D
0.99
0.94
1.00
G1UA048S17
0.98
1.00
1.00
G1UA048S21,24
1.00
1.00
1.00
G1UA060S21,24
1.02
1.03
1.00
G2FD042S21
0.96
0.96
0.99
G2FD046S17
0.98
0.98
1.00
G2FD048S21,24
1.00
1.00
1.01
G2FD060S24
1.02
1.02
1.00
MDD48DSD
0.99
0.94
1.00
Air Handler
Coil
T.C.
S.C.
KW
N1AHC1646
G2FD042S21
0.98
0.99
1.00
N1AHC1646
G2FD048S21
0.99
1.01
1.01
F2RP/F2FP042
0.95
0.95
0.99
F2FP048
0.99
0.99
0.99
G1FA060S21,24
1.02
1.02
1.00
G1NA036S21C
0.98
0.93
0.99
G1NA048S21D
0.99
0.94
1.00
G1UA048S21,24
1.00
1.00
1.00
G1UA060S21,24
1.02
1.03
1.00
G2FD042S21
0.96
0.96
0.99
G2FD046S17
0.98
0.98
1.00
G2FD048S21,24
1.00
1.00
1.01