Typical field control wiring diagram, Typical field power wiring diagram, 13 additional static pressure resistance – York AFFINITY 291627-YTG-B-0807 User Manual

Page 17: 1/2 - 5 ton (dnh042 - 060), Programmable thermostat only, Thermostat unit terminal strip, 24 volt transformer

background image

291627-YTG-B-0807

Unitary Products Group

17

FIGURE 3 - TYPICAL FIELD CONTROL WIRING DIAGRAM

FIGURE 4 - TYPICAL FIELD POWER WIRING DIAGRAM

TABLE 13: ADDITIONAL STATIC PRESSURE RESISTANCE 3-1/2 - 5 TON (DNH042 - 060)

1

DESCRIPTION

RESISTANCE, IWG

CFM

1,100

1,200

1,300

1,400

1,500

1,600

1,700

1,800

1,900

2,000

WET EVAPORATOR COIL

.02

.03

.04

.05

.06

.07

.07

.08

.09

.09

ECONOMIZER

2

.02

.02

.02

.03

.03

.04

.04

.04

.05

.05

FILTER FRAME KIT

.04

.04

.05

.05

.06

.07

.08

.09

.10

.11

1. Deduct these resistance values from the available external static pressure shown in Table 8, 9, 10, and 11
2. The pressure through the economizer is greater for 100% outdoor air then for 100% return air. If the resistance of the return air

duct system is less then 0.25 IWG, the unit will deliver less CFM during full economizer operation.

R

G

W

R

G

C

Y

Y

W

C

PROGRAMMABLE

THERMOSTAT ONLY

**

** = Minimum wire size of 18 AWG

wire should be used for all
field installed 24 volt wire.

THERMOSTAT

UNIT TERMINAL STRIP

NOTE:
HEAT ANTICIPATOR
SHOULD BE SET AT 0.35
AMPS FOR ALL MODELS.

24 VOLT
TRANSFORMER

CONTACTOR

GROUND

LUG

FIELD-SUPPLIED

DISCONNECT

REFER TO ELECTRICAL
DATA TABLES TO SIZE
THE DISCONNECT

THREE
PHASE
POWER
SUPPLY