Typical field control wiring diagram, Typical field power wiring diagram, 13 additional static pressure resistance – York AFFINITY 291627-YTG-B-0807 User Manual
Page 17: 1/2 - 5 ton (dnh042 - 060), Programmable thermostat only, Thermostat unit terminal strip, 24 volt transformer
291627-YTG-B-0807
Unitary Products Group
17
FIGURE 3 - TYPICAL FIELD CONTROL WIRING DIAGRAM
FIGURE 4 - TYPICAL FIELD POWER WIRING DIAGRAM
TABLE 13: ADDITIONAL STATIC PRESSURE RESISTANCE 3-1/2 - 5 TON (DNH042 - 060)
1
DESCRIPTION
RESISTANCE, IWG
CFM
1,100
1,200
1,300
1,400
1,500
1,600
1,700
1,800
1,900
2,000
WET EVAPORATOR COIL
.02
.03
.04
.05
.06
.07
.07
.08
.09
.09
ECONOMIZER
2
.02
.02
.02
.03
.03
.04
.04
.04
.05
.05
FILTER FRAME KIT
.04
.04
.05
.05
.06
.07
.08
.09
.10
.11
1. Deduct these resistance values from the available external static pressure shown in Table 8, 9, 10, and 11
2. The pressure through the economizer is greater for 100% outdoor air then for 100% return air. If the resistance of the return air
duct system is less then 0.25 IWG, the unit will deliver less CFM during full economizer operation.
R
G
W
R
G
C
Y
Y
W
C
PROGRAMMABLE
THERMOSTAT ONLY
**
** = Minimum wire size of 18 AWG
wire should be used for all
field installed 24 volt wire.
THERMOSTAT
UNIT TERMINAL STRIP
NOTE:
HEAT ANTICIPATOR
SHOULD BE SET AT 0.35
AMPS FOR ALL MODELS.
24 VOLT
TRANSFORMER
CONTACTOR
GROUND
LUG
FIELD-SUPPLIED
DISCONNECT
REFER TO ELECTRICAL
DATA TABLES TO SIZE
THE DISCONNECT
THREE
PHASE
POWER
SUPPLY