10 bottom supply air blower performance, 208 volt – York AFFINITY 291627-YTG-B-0807 User Manual
Page 15
291627-YTG-B-0807
Unitary Products Group
15
TABLE 10: BOTTOM SUPPLY AIR BLOWER PERFORMANCE - 208 VOLT
1
MODEL #
DNH
(Cooling/
Heating)
MTR
SPD
EXTERNAL STATIC PRESSURE - IWG
.10
.20
.30
.40
.50
.60
.70
.80
.90
1.00
1.10
CF
M
W
A
TTS
CF
M
W
A
TTS
CF
M
W
A
TTS
CF
M
W
A
TTS
CF
M
W
A
TTS
CF
M
W
A
TTS
CF
M
W
A
TTS
CF
M
W
A
TTS
CF
M
W
A
TTS
CF
M
W
A
TTS
CF
M
W
A
TTS
030
HI
-
-
-
-
1115 454 1049 436
967
417
886
398
805
380
676
351
-
-
-
-
-
-
MED
895
300
853
289
811
278
769
267
697
252
-
-
-
-
-
-
-
-
-
-
-
-
LOW
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
036
HI
-
-
-
-
-
-
-
-
1458 688 1377
663
1295 639 1147 600
999
561
-
-
-
-
MED
1482 628 1428 613 1374 599 1320 584 1242 556 1163
528
1085 500
961
474
-
-
-
-
-
-
LOW
1239 510 1184 496 1130 481 1075 467
998
448
922
428
-
-
-
-
-
-
-
-
-
-
042
HI
-
-
1687 763 1614 737 1540 712 1458 688 1377
663
1295 639 1147 600
-
-
-
-
-
-
MED
1482 628 1428 613 1374 599 1320 584 1242 556 1163 -528 1085 500
-
-
-
-
-
-
-
-
LOW
1239 510 1184 496 1130 481 1075 467
-
-
-
-
-
-
-
-
-
-
-
-
-
-
048
HI
1655 771 1609 749 1563 727 1504 698 1444 670 1381
648
1319 626
-
-
-
-
-
-
-
-
MED
1499 687 1474 670 1449 653 1400 630 1351 606 1297
583
1242 559
-
-
-
-
-
-
-
-
LOW
1418 610 1388 593 1357 576 1327 561 1298 546 1241
523
-
-
-
-
-
-
-
-
-
-
060
(3 tube)
HEAT
1500 245 1500 297 1500 348 1500 400 1500 470 1500
540
1500 610 1500 680 1500 750 1500 820 1500 890
060
(4 & 5 tube)
HEAT
1700 390 1700 443 1700 497 1700 550 1700 620 1700
690
1700 760 1700 830 1700 900
-
-
-
-
060
(factory
settings)
COOL 1800 460 1800 515 1800 570 1800 625 1800 690 1800
755
1800 820 1800 962
-
-
-
-
-
-
060
(field settings)
COOL 2000 640 2000 700 2000 760 2000 820 2000 928
-
-
-
-
-
-
-
-
-
-
-
-