PROCEDURES:

1. Unit factory charge listed on the unit nameplate includes refrigerant for the condenser, the smallest evaporator and 15 feet of

interconnecting line tubing.

2. Verify the TXV and additional charge required for specific evaporator coil in the system using the above table.
3. Additional charge for the amount of interconnecting line tubing greater than 15 feet at the rate specified in the table above.
4. Permanently mark the unit nameplate with the total system charge. Total System Charge = Base Charge (as shipped) + adder for

evaporator + adder for line set.

FC/MC/PC48D3X

702 + 12

703 + 9*

FC/PC60C3X

703 + 13

703 + 6*

2C + 0*

FC/MC/PC60D3X

703 + 13

703 + 6*

2C + 0*

MC61D3X

703 + 13

2C + 0

FC/MC62D3X

703 + 13

2C + 0

HC30A3X

2A + 0

HC36B3X

2A + 0

2A + 0

HC42C3X

702 + 9

703 + 6*

HC60D3X

703 + 13

703 + 6*

2C + 0*

HD24A3X

HD36B3X

2A + 0

2A + 0

702 + 5

HD48C3X

703 + 0*

703 + 0*

HD60D3X

2C + 0*

UC24A3X

2A + 0

UC24B3X

2A + 0

UC30A3X

2A + 0

UC30B3X

2A + 0

UC36A3X

2A + 0

UC36B3X

2A + 0

UC36C3X

2A + 0

UC42B3X

702 + 0

UC42C3X

702 + 0

UC48C3X

702 + 12

703 + 9*

UC48D3X

702 + 12

703 + 9*

UC60C3X

703 + 13

703 + 6*

2C + 0*

UC60D3X

703 + 13

703 + 6*

2C + 0*

AHP24B3X

2A + 0

AHP30B3X

2A + 0

2A + 0

AHP42C3X

702 + 9

AHP/SHP48D3X

703 + 13

703 + 6*

AHP/SHP60D3X

702 + 17

703 + 13

703 + 6

2C + 0

AV24B3X

2A + 0

AV36C3X

2A + 0

2A + 0

702 + 9

AV/SV48D3X

703 + 13

703 + 6

AV/SV60D3X

703 + 13

703 + 6

2C + 0

F*FP040

2A + 0

F4FV060H06T2C

703 + 6

0

FOOTNOTES:

1. A TXV kit must be used with these coils to obtain system performance.
2. Systems matched with furnace or air handlers not equipped with blower-off delays may require blower Time Delay Kit 2FD06700224.
3. PC coils cannot be used in downflow or horizontal applications. FC coils cannot be used in horizontal applications.
4. If no TXV is listed, the indoor coil has the correct valve factory installed.
* Does not achieve 14 SEER with PSC furnaces. For ratings, see technical guide or visit www.aridirectory.org/ari/unitary.html

Additional R-22 Charge / Orifice Size for Various Matched Systems - 1 Phase (Continued)

Outdoor Unit

HABE-F018S

HDBE-F024S

HCBE-F030S

HABE-F036S

HBBE-F042S

HBBE-F048S

HCBE-F060S

Required TXV

1

1TVM2A1

1TVM2A1

1TVM2A1

1TVM702

1TVM703

1TVM703

1TVM2C1

Factory Charge, lbs-oz

5 - 9

6 - 0

8 - 2

9 - 14

14 - 15

15 - 5

16 - 5

Indoor Coil

2,3

TXV

4

+ Charge Adder, Oz