York H*BE-F018 User Manual
Page 14
332018-BTG-D-0208
14
Unitary Products Group
Multipliers for determining the performance with other indoor sections.
NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the
listed temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.
COOLING PERFORMANCE DATA
AIR CONDITIONER MODEL NO.
HBBE-F042S
INDOOR COIL MODEL NO.
FC/MC/PC/UC60
CONDENSER
ENTERING AIR
TEMPERATURE
ID CFM
1300
1450
1550
ID DB
85
80
75
70
85
80
75
70
85
80
75
70
ID WB
72
67
62
57
72
67
62
57
72
67
62
57
75
T.C.
47.3
43.8
40.3
37.2
47.7
44.3
40.9
37.7
48.0
44.5
41.2
38.0
S.C.
28.3
28.5
28.9
29.2
29.8
30.0
30.6
30.7
30.8
31.0
31.6
31.7
K.W
2.88
2.84
2.80
2.77
2.95
2.90
2.87
2.84
3.00
2.95
2.91
2.88
85
T.C.
44.6
41.3
38.1
35.1
45.0
41.8
38.6
35.5
45.2
42.1
38.8
35.9
S.C.
27.4
27.6
28.1
28.2
29.0
29.2
29.6
29.8
30.0
30.2
30.6
30.8
K.W
3.14
3.10
3.06
3.04
3.20
3.16
3.13
3.11
3.25
3.21
3.17
3.15
95
T.C.
42.2
39.0
36.0
33.1
42.5
39.5
36.4
33.7
42.8
39.7
36.6
33.9
S.C.
26.6
26.8
27.2
27.4
28.2
28.4
28.7
28.9
29.3
29.4
29.7
29.8
K.W
3.45
3.41
3.39
3.37
3.52
3.48
3.45
3.43
3.56
3.52
3.49
3.47
105
T.C.
39.7
36.8
33.9
31.2
40.1
37.2
34.2
31.8
40.3
37.3
34.4
32.2
S.C.
25.9
26.1
26.4
26.6
27.5
27.6
27.9
28.2
28.5
28.5
28.9
28.6
K.W
3.82
3.79
3.77
3.75
3.89
3.86
3.83
3.81
3.93
3.90
3.87
3.85
115
T.C.
37.2
34.5
31.7
29.3
37.6
34.8
32.1
30.0
37.8
35.0
32.3
30.3
S.C.
25.1
25.2
25.5
25.6
26.7
26.7
27.1
26.6
27.7
27.7
27.9
26.9
K.W
4.26
4.23
4.21
4.19
4.32
4.29
4.27
4.26
4.36
4.34
4.31
4.30
125
T.C.
34.7
32.2
29.5
27.4
35.1
32.4
30.0
28.2
35.3
32.7
30.2
28.4
S.C.
24.3
24.3
24.6
24.6
25.9
25.8
26.3
25.0
26.9
26.9
26.9
25.2
K.W
4.70
4.67
4.65
4.63
4.75
4.72
4.71
4.71
4.79
4.78
4.75
4.75
NOTE: ALL CAPACITIES INCLUDE INDOOR FAN HEAT AT 1250 BTUH/1000 CFM.
Air Handler
Coil
T.C.
S.C.
KW
AHP/SHP48
–
1.00
1.01
1.00
AV/SV48
–
1.00
1.01
0.96
AV/SV60
–
1.00
1.01
0.96
AHP/SHP60
–
1.00
1.01
0.96
MA14D
FC/MC48D
0.98
0.98
1.02
MA14D
FC/MC60D
1.00
1.00
1.00
MA16C
FC60C
1.00
1.00
1.00
MV16C
FC/MC48C
1.00
0.98
1.00
MV20D
FC/MC60D
1.02
1.00
1.02
–
FC/MC/PC/UC48
0.98
0.98
1.02
–
HC48
0.96
0.96
1.01
–
HC60
0.99
1.00
0.99
–
HD48
0.96
0.96
1.01
–
HD60
0.99
0.96
0.99
Variable Speed
Furnace
Coil
T.C.
S.C.
KW
(F,L)L8V*C16
FC/MC/PC48C
0.99
0.97
0.99
(F,L)L8V*C16
FC/PC60C
0.99
0.97
0.99
(F,L)L8V*C20
FC/MC/PC48C
0.99
0.97
0.99
(F,L)L8V*C20
FC/PC60C
1.01
1.00
1.01
(F,L)L8V*C20
HC60
1.01
1.00
1.01
(F,L)L8V*C20
HD60
1.01
1.00
1.01
FL9(C,V)*C16
FC/MC/PC48C
0.98
0.96
0.98
FL9(C,V)*C16
FC/PC60C
1.00
0.98
1.00
FL9(C,V)*C20
FC/MC/PC48C
0.98
0.96
0.98
FL9(C,V)*C20
FC/PC60C
1.00
0.98
1.00
FL9(C,V)*C20
HD60
1.00
0.98
1.00
FL9(C,V)*D20
FC/MC/PC48D
0.98
0.96
0.98
FL9(C,V)*D20
FC/MC/PC60D
1.00
0.98
1.00
FL9(C,V)*D20
HC60
1.00
0.98
1.00
FL9(C,V)*D20
HD60
1.00
0.98
1.00