Electrical Work

Defrosting operation (Available for heating only)

1. Condition to start defrosting: Units will switch to defrosting

mode when either of the following conditions is met.

a. Unit has been running under T3<0ºC for 40

minutes and T3<-3ºC for 3 minutes.

b. Unit has been running at high temperature

protection mode* for 90 minute. (*High temperature
protection mode: when coil temperature of indoor
unit reaches 55°C, outdoor unit will turn off external
unit fan but still keep compressor running).

2. Condition to stop defrosting: Units will switch back to

heating mode when either of the following conditions
is met.

a. Unit has been running at defrosting mode for 10

minutes.

b. T3>20

ºC

Remark: T3 is coil temperature of outdoor units.

0

-1

-2

-3

-4

-5

1

2

0

5

10 15 20 25 30 35 40 45 50

T3 (°C)

3 min

40 min

Heating mode

Defrosting mode

Time
Elapsed
(min)

Starting Defrosting Mode under condition a.

NOTE

The supply volyage must be consistent with the rate voltage of the air conditioner.

Wiring size

Switch and

Fuse rating

Power Source

Model

f

f

f

f

f 1.0 mm

2

10A

220-240V ~ 50Hz

220-230V ~ 60Hz

7000-9000 Btu/h

f

f

f

f

f 1.5 mm

2

16A

12000 Btu/h

f

f

f

f

f 2.5 mm

2

25A

18000 Btu/h

32A

24000 Btu/h

220-240V ~ 50Hz

220-230V ~ 60Hz

220-240V ~ 50Hz

220-230V ~ 60Hz

220-240V ~ 50Hz

220-230V ~ 60Hz