To this effect, when the piping has been evacuated, close the pressure gauge tap, note the value on the gauge, then
wait for 15 minutes. If the needle moves, there is a leak in the system. Make the necessary adjustments or repairs and
repeat this procedure until the needle no longer moves.

- Open the service valves and top up the refrigerant charge if necessary.

Installation

Minimum thickness 6 mm

Heat pump

Liquid

Cooling

Heat pump
(discharge)

Cooling

(suction)

Heat pump
(discharge)

Heat pump

This unit is shipped complete with a charge of R22/R407C/R 410A
refrigerant that will be sufficient for an interconnecting piping length
of 5 meters.

Liquid

Cooling

GAS

Cooling

(suction)

Low pressure

High pressure

Manifold

Gas valve

Liquid valve

Pressure tap

Outdoor unit

Indoor unit

Gas line

Liquid line

R22/R407C/R410A

- Outdoor heat pump unit : install the unit at least 10 cm above ground level to facilitate drainage of defrost water and

prevent accumulation of ice. In effect, defrost water can cause accumulation of ice under the unit during subfreezing
outdoor temperatures.

- In areas with heavy snowfall it is best to install the unit on wall supports.
- In some regions. It is necessary to heat the bottom of the condensate drainage pan and the condensate drainage

piping to avoid ice formation, and resulting ice build-up in the fan compartment (heater strip must be at least 25 w/m).

COLD AREA RECOMMENDATION

OK