20ma output, Zone 1 4-20ma output field calibration procedure – Watlow Series 733 Service User Manual

Page 28

background image

28

WATLOW Series 733/734 Service Manual

Calibration, Chapter 5

4-20mA Output

˜

NOTE:
Before calibration
on an installed
control, make sure
all data and para-
meters are docu-
mented. See Setup
and Service Tables,
Pages 16 and 19.

The calibration procedure for Zone 1 and Zone 2 are the same
except use the Ot2L and Ot2H parameters for Zone 2.

Zone 1 4-20mA Output Field Calibration Procedure

For model #:

73XX-XFXX-XXXX

73XX-XXFX-XXXX

73XX-XFFX-XXXX

Equipment Required

300 , 1/2 watt 10% resistor.

• 4 - 1/2 digit Digital Multimeter.

Setup And Calibration

˜

1.

Connect the AC line voltage L1 and L2 to the proper terminals of the 733/734.

2.

Connect the multimeter in series with the 300 resistor to Output connector
#2 Negative and #3 Positive for Zone 1.

3.

Apply power to the unit and allow it to warm up for 15 minutes. After warm-up
put the unit in the Calibration mode. See the beginning of this chapter At the
CALy parameter, select OUt. Press the Time key.

4.

At the Ot1L prompt, the multimeter should read approximately 4mA. Allow at
least 10 seconds to stabilize.

5.

Use the Up/Down keys (reverse acting) to adjust the reading on the
multimeter for 3.85mA ± 0.10mA. Press the Time key.

6.

At the Ot1H prompt, the multimeter should read approximately 20mA. Allow
at least 10 seconds to stabilize.

7.

Use the Up/Down keys (reverse acting) to adjust the reading on the
multimeter for 20.15mA ±0.10 mA.

8.

For dual 4-20mA output control, connect the multimeter in series with the
300 resistor to Output connector #4 Negative and #1 Positive. Use regular
20 - 24 gauge wire. Repeat steps 4 through 7 using the Ot2L and Ot2H
prompts.