WATLOW Series 733/734 Service Manual

Service Mode, Chapter 3

Service

Display alternates
between parameter and
programmed data.

0

AUt1

AUt2

0

Pb1

25

rE1

0.00

rA1

0.00

Ct1

5

Pb2

25

rE2

0.00

0.00

rA2

Service Parameters

Auto-tune Zone 1: Initiates auto-tune for Zone 1. For more information on tuning,
see Chapter 4, Page 19.
Range: 0 = off, 1 = slow, 2 = medium, 3 = fast

Default: 0

Auto-tune Zone 2: Initiates auto-tune for Zone 2. For more information on tuning,
see Chapter 4, Page 19.
Range: 0 = off, 1 = slow, 2 = medium, 3 = fast

Default: 0

Proportional Band 1: A proportional band expressed in degrees F or C, within
which a controller proportioning function is active for Zone 1. When Pb1 = 0, it
functions as an ON/OFF control. The switching differential is then determined by
the HYS1 parameter in the Setup mode. See Page 15.
Range: 0 to 999°F/0 to 555°C

Default: 25°F

Reset 1: A reset (integral) control action for Zone 1 automatically eliminates offset,
or "droop," between set point and actual process temperature in a proportional
control. This parameter only appears if Pb1 0.
Range: 0.00 to 9.99 repeats/minute

Default: 0.00

Rate 1: The rate (derivative) function for Zone 1 which affects the speed or rate at
which the process temperature approaches the set point to minimize overshoot
and/or undershoot. The rate is determined by how fast the error is changing. This
parameter only appears if Pb1 0.
Range: 0.00 to 9.99 minutes

Default: 0.00

Cycle Time 1: Expressed in seconds, time for a controller to complete one ON/
OFF cycle for Zone 1. Time between successive turn ons. This parameter only
appears if Pb1 0.
Range: 1 to 60 seconds

Default: 5

Proportional Band 2: A proportional band expressed in degrees or process units,
within which a controller proportioning function is active for Zone 2. When Pb2 = 0,
it functions as an ON/OFF control. The switching differential is then determined by
the HYS2 parameter. This parameter only appears if you have a dual zone control.
Range: 0 to 999°F/0 to 555°C/0 to 999 units

Default: 25°F

Reset 2: A reset (integral) control action for Zone 2 automatically eliminates offset,
or "droop," between set point and actual process temperature in a proportional
control. This parameter only appears if your unit has a secondary output and Pb2

0.

Range: 0.00 to 9.99 repeats/minute

Default: 0.00

Rate 2: The rate (derivative) function for Zone 2 which affects the speed or rate at
which the process temperature approaches the set point to minimize overshoot
and/or undershoot. The rate is determined by how fast the error is changing. This
parameter only appears if your unit has a secondary output and Pb2 0.
Range: 0.00 to 9.99 minutes

Default: 0.00